Breaker Size Calculator
Calculate the correct circuit breaker size for any load. Enter watts and voltage to get the proper breaker rating per NEC standards.
Standard Breaker Sizes Chart
| Breaker Size | Max Load (240V) | Max Load (120V) | Wire Size | Common Uses |
|---|---|---|---|---|
| 15A | 2,880W | 1,440W | 14 AWG | Lighting, outlets |
| 20A | 3,840W | 1,920W | 12 AWG | Kitchen, bathroom, garage |
| 30A | 5,760W | 2,880W | 10 AWG | Water heater, AC condenser |
| 40A | 7,680W | 3,840W | 8 AWG | Range, EV charger (Level 2) |
| 50A | 9,600W | 4,800W | 6 AWG | Large range, spa |
| 60A | 11,520W | 5,760W | 6 AWG | EV charger, sub-panel |
| 100A | 19,200W | 9,600W | 2 AWG | Main panel, large sub-panel |
NEC Breaker Sizing Rules
- Continuous loads (3+ hours): Size breaker at 125% of load current
- Non-continuous loads: Size breaker at 100% of load current
- Motor loads: Size breaker at 175-250% of full-load amps (starting current)
- Next size up rule: If calculated size isn't standard, go to next standard size
- Wire must be sized to match the breaker, not the load
- Solar DC breakers: Size at 125% of short-circuit current (Isc)
What size breaker do I need for a 2400W water heater?
2400W / 240V = 10A. With 125% safety factor: 12.5A → use a 15A breaker with 14 AWG wire. Most water heaters use a 30A breaker (allowing for larger units).
How do I size a breaker for solar panels?
For solar DC breakers: Take the panel short-circuit current (Isc) × number of parallel strings × 1.25 (NEC continuous) × 1.25 (irradiance safety). For example, 2 strings of panels with 10A Isc each: 10 × 2 × 1.25 × 1.25 = 31.25A → use a 30A DC breaker.
What size breaker for a Level 2 EV charger?
Most Level 2 EV chargers draw 32-40A continuously. With 125% safety factor: 40-50A → use a 50A breaker with 6 AWG wire. Check your charger's specs for exact requirements.