Sizing PV and Battery Conductors: Ampacity, Derating and Voltage Drop
Three checks decide every DC conductor: code ampacity, conditions-of-use derating, and voltage drop. Getting one right and two wrong is how systems fail inspection or underperform.
Conductor sizing is not one calculation. It is three, applied in a fixed order: start from 1.25× the continuous current (Isc for PV source circuits, continuous output for battery circuits), apply the conditions-of-use correction factors for temperature and conduit fill, then check the voltage drop over the actual run. Skipping the derating step is the most common error - a conductor that is fine at 30°C in free air is not fine in a rooftop conduit at 60°C.
| Check | Rule of thumb | Failure mode if missed |
|---|---|---|
| Code ampacity | 1.25× Isc (PV) or 1.25× continuous current (battery) | Undersized conductor, failed inspection |
| Conditions of use | Derate for ambient temperature and conduit fill (NEC 310.15) | Conductor overheats in a hot rooftop raceway |
| Voltage drop | ≤2-3% on the DC run for a well-performing system | Array produces but the inverter sees less; output lost silently |
| Termination rating | Confirm 75°C vs 90°C terminals | Derated ampacity used incorrectly at the lug |
Battery circuits carry high continuous current at low voltage. At 48V, a 10kW discharge is roughly 210A - that is 4/0 copper territory, and the voltage drop over a 20-foot run is material. Higher-voltage batteries reduce the current and therefore the conductor, which is why architecture decisions change the wire bill more than the wire selection does.
-
1
Establish the design current
PV source circuits: 1.25 × Isc. Battery circuits: 1.25 × continuous inverter input current at minimum battery voltage.
-
2
Apply temperature correction
Use the ambient temperature of the raceway location, not the outdoor design temperature, then apply the conduit-fill factor.
-
3
Select the conductor
Pick the smallest conductor whose derated ampacity still exceeds the design current - not the largest that fits the lug.
-
4
Compute voltage drop on the real run
Use round-trip length. A 3% drop at 48V/200A costs real output and heat.
-
5
Verify termination and OCPD compatibility
Confirm the breaker/fuse rating, the terminal temperature rating, and that the conductor fits the equipment lug.
What voltage drop is acceptable on a PV DC circuit?
Can I upsize PV wire to reduce voltage drop?
Does the same conductor work in conduit and in free air?
Price PV wire and battery cable for your run
Get trade pricing, freight quotes, and portal calculators.
Register NowWhere to source it
Send a list to the quote desk for line-item trade pricing and freight.
Popular items in this category
- #10 AWG USE-2/PV (+), (2) #10 AWG USE-2/PV (−) per route; #6 bare Cu EGC (protec
- #10 THWN-2 250' Black
- #10 THWN-2 500' Black
- #10 THWN-2 250' RED
- #10 THWN-2 500' RED
- #6 bare CU grounding wire 315'
- #6 bare CU grounding wire 350'
- #6 CU grounding wire 350'
Trade pricing and freight on any of these: quote desk.