Powering Telecom and Remote Sites: Solar, Battery and DC Plant Design
Remote telecom sites are the hardest power problem in the catalogue: unattended, deep-cycle, often 24/48V DC and sometimes required to run through a week of bad weather.
A telecom site cannot shed load when the weather turns. Design starts with the DC load (often 24V or 48V at a few hundred watts), the required days of autonomy, and the site's worst-month insolation. A site that runs on 500W average becomes a 3-4kW array once the winter derate and autonomy are applied.
DC-coupled architectures dominate here: the load is natively DC, so avoiding an inverter removes a conversion loss and a failure point.
| Input | Typical value | Drives |
|---|---|---|
| DC load | 200-600W continuous | Battery kWh and array size |
| System voltage | 24V or 48V DC | Conductor sizing and equipment selection |
| Autonomy | 3-7 days | Battery bank size - the dominant cost |
| Worst-month insolation | 2-4 kWh/m2/day | Array wattage |
| Temperature range | -30 to +50°C | Battery chemistry choice and enclosure thermal design |
LFP gives usable depth and cycle life but needs thermal management where winters are hard - charging below freezing damages cells. AGM or gel tolerates cold charging but gives roughly half the usable capacity and a shorter cycle life. Many operators end up with a heated LFP enclosure plus a generator for the worst weeks; the generator is the cheapest kilowatt-hour of autonomy.
-
1
Establish the DC load profile
Average and peak current at the system voltage, including radio equipment duty cycles and any heating.
-
2
Choose system voltage
24V for smaller loads, 48V above roughly 1kW to keep conductor sizes sane over long runs.
-
3
Size the battery for autonomy
Use usable kWh, apply a temperature derate, and accept the generator as the last line of defence.
-
4
Size the array for the worst month
Worst-month insolation plus a soiling/snow allowance; oversizing here is cheaper than more battery.
-
5
Design the enclosure
Thermal management, ventilation, intrusion and remote monitoring - the site is unattended by definition.
Why do telecom sites use 48V DC?
Is LFP suitable in cold climates?
Do remote sites still need a generator?
Plan a remote site power system with us