Voltage Drop
--

Wire Resistance (Ohms per 1000 ft, Copper)

AWG Resistance (Ω/1000ft) Ampacity (75°C) Max Distance @3% (30A, 240V)
14 AWG 2.525 20A 47 ft
12 AWG 1.588 25A 75 ft
10 AWG 0.999 35A 119 ft
8 AWG 0.628 50A 189 ft
6 AWG 0.395 65A 301 ft
4 AWG 0.249 85A 477 ft
2 AWG 0.156 115A 762 ft