Voltage Drop Calculator: NEC 3%/5% Rule, Formula & Wire Size Charts

PES Supply, a PES Global Group Company
· 12 min read PES Engineering Desk — reviewed by a licensed master electrician
Voltage drop calculator hero — cable run with voltage waveform, Portlandia Electric Supply

Table of Contents

    Voltage drop is the silent killer of otherwise well-designed electrical systems. A run of wire that looks fine on paper can leave the motor at the far end starved of voltage, running hot, tripping overloads, and dying years early. The National Electrical Code doesn't set a hard legal limit for voltage drop on branch circuits, but the NEC's informational notes (210.19(A) Informational Note No. 4 and 215.2(A)(1) Informational Note No. 2) point designers to the same targets the industry has used for decades: keep a branch circuit under 3% and keep the total of feeder plus branch under 5%. This guide gives you a working calculator, the actual math, and the reference tables to check any run by hand.

    If you already know your ampacity requirement and just need the wire size, our Wire Ampacity Calculator (NEC 310.16) handles that side of the problem. Voltage drop and ampacity are separate checks — a conductor can pass one and fail the other — and both must pass before you pull wire.

    Voltage Drop Calculator

    NEC 3% branch-circuit / 5% combined guidance · single-phase & three-phase · copper & aluminum

    Voltage drop—
    Percent of system voltage—
    NEC 3% branch guidance—
    Recommended size for ≤3%—
    This run meets the 3% branch-circuit guideline. Still verify ampacity and the 5% feeder-plus-branch total.
    Exceeds 3% — upsize the conductor (recommendation above) or shorten the run. Check the 5% combined feeder + branch budget too.

    Method: VD = 2·K·L·I ÷ circular mils (single-phase); VD = √3·K·L·I ÷ CM (three-phase). K = 12.9 Ω·cmil/ft for copper, 21.2 for aluminum at 75 °C. Always confirm ampacity per NEC 310.16 and breaker sizing per the 125% rule.

    The Voltage Drop Formula, Explained Plainly

    Every conductor is a resistor. Push current through it and some of the system voltage is spent overcoming that resistance instead of doing useful work at the load. The standard single-phase formula used throughout the industry is:

    VD = 2 × K × L × I ÷ CM

    where L is the one-way conductor length in feet (the "2" accounts for the round trip out and back), I is load current in amps, CM is the conductor's cross-sectional area in circular mils, and K is the resistivity constant: approximately 12.9 ohm-circular-mils per foot for copper and 21.2 for aluminum at 75 °C. For three-phase systems the round-trip geometry changes, so the multiplier is √3 instead of 2:

    VD3φ = 1.732 × K × L × I ÷ CM

    To express the drop as a percentage — the number the NEC guidance actually references — divide by the system voltage and multiply by 100. A 7.2 V drop means very different things on a 120 V circuit (6%) and a 480 V circuit (1.5%), which is why percentage, not volts, is the design criterion.

    Worked Example 1: A 240 V Well Pump That Barely Passes

    A 240 V single-phase well pump draws 30 A and sits 150 feet from the panel. An installer reaches for 10 AWG copper because the NEC 310.16 ampacity chart says 10 AWG copper handles 35 A at 75 °C. Ampacity passes. Now check the drop:

    VD = 2 × 12.9 × 150 × 30 ÷ 10,380 = 11.18 V = 4.66%

    That fails the 3% branch guideline even though the wire is perfectly safe from an overheating standpoint. Stepping up to 8 AWG copper (16,510 cmil) gives VD = 7.02 V = 2.93% — a pass. This is the classic long-run trap: on short runs ampacity governs, on long runs voltage drop governs, and the crossover happens sooner at lower voltages.

    Worked Example 2: Three-Phase 480 V Feeder

    A 480 V three-phase load draws 100 A over a 200-foot run using 3/0 aluminum (167,800 cmil):

    VD = 1.732 × 21.2 × 200 × 100 ÷ 167,800 = 4.38 V = 0.91%

    Comfortably under 3% — higher system voltages are far more forgiving, which is exactly why commercial distribution runs at 480 V and long solar strings run at 600–1000 V. If you're designing PV source circuits, our PV wire voltage options guide and the MC4 wire gauge guide cover the DC side, where 2% is the common design target.

    Conductor Reference: Circular Mils by Size

    The calculator above uses these NEC Chapter 9, Table 8 values. Print it, save it, or just trust the tool:

    Size Circular mils Size Circular mils
    14 AWG 4,110 2/0 AWG 133,100
    12 AWG 6,530 3/0 AWG 167,800
    10 AWG 10,380 4/0 AWG 211,600
    8 AWG 16,510 250 kcmil 250,000
    6 AWG 26,240 350 kcmil 350,000
    4 AWG 41,740 500 kcmil 500,000
    2 AWG 66,360 750 kcmil 750,000

    Maximum One-Way Run for a 3% Drop (Copper, Common Cases)

    This table shows how fast voltage drop eats your budget at 120 V versus 240 V. Values are one-way feet for copper conductors at full load:

    Load Wire Max run @120 V (3%) Max run @240 V (3%)
    15 A 14 AWG Cu 47 ft 93 ft
    20 A 12 AWG Cu 56 ft 112 ft
    20 A 10 AWG Cu 89 ft 178 ft
    30 A 10 AWG Cu 59 ft 119 ft
    30 A 8 AWG Cu 95 ft 189 ft
    40 A 8 AWG Cu 71 ft 142 ft
    50 A 6 AWG Cu 90 ft 180 ft
    100 A 2 AWG Cu 114 ft 228 ft

    The pattern is unmistakable: doubling the system voltage doubles the allowable distance, and dropping from 240 V to 120 V halves it. For long outbuilding or gate-operator runs, stepping up to 240 V (or 480 V three-phase) is often cheaper than buying thicker copper.

    Maximum One-Way Run for a 3% Drop (480 V Three-Phase, Copper)

    Commercial feeders at 480 V three-phase get enormous distance budgets because the percentage denominator is large and the 1.732 multiplier beats the single-phase 2×. One-way feet at full load:

    Load Wire (Cu) Max run @480 V 3φ (3%) Max run @208 V 3φ (3%)
    50 A 6 AWG 451 ft 196 ft
    100 A 2 AWG 570 ft 247 ft
    150 A 2/0 AWG 633 ft 274 ft
    200 A 4/0 AWG 760 ft 329 ft
    300 A 350 kcmil 839 ft 363 ft
    400 A 500 kcmil 900 ft 389 ft

    At 480 V, a 200 A load can travel three-quarters of a football field on 4/0 copper before drop becomes a design constraint. At 208 V the same wire is spent at 329 feet — one reason 208 V wye services deserve closer scrutiny on spread-out commercial sites.

    Feeder vs. Branch: Splitting the 5% Budget

    The 5% figure is a combined allowance: feeder plus branch together. In practice designers allocate it deliberately — a common split is 2% to the feeder and 3% to the branch, but any split that sums to 5% works. On a long service to a detached building, it often makes sense to give the feeder 2.5–3% (one fat efficient run) and leave 2–2.5% for branch circuits inside the building. Run the calculator twice — once for the feeder segment, once for the branch — and add the percentages. Forgetting that the budget is shared is how a building full of individually compliant circuits ends up with dimming lights at the end of the line.

    Constants Quick Card

    Constant Value When to use it
    K — copper 12.9 Ω·cmil/ft All copper voltage-drop work at 75 °C
    K — aluminum 21.2 Ω·cmil/ft All aluminum voltage-drop work at 75 °C
    Single-phase multiplier 2 120/240 V split-phase circuits (round trip)
    Three-phase multiplier 1.732 (√3) 208/240/480 V balanced three-phase, line-to-line volts
    Branch-circuit target ≤3% Panel to final load
    Combined target ≤5% Feeder + branch added together
    Solar DC design target ≤1.5–2% PV strings — stricter than NEC guidance

    Copper vs. Aluminum: The 21.2 vs. 12.9 Trade-Off

    Aluminum's K constant is about 64% higher than copper's, so for the same size and load, aluminum drops roughly 1.64× the voltage. The practical rule of thumb is to go two sizes larger when you switch from copper to aluminum — 2 AWG aluminum behaves approximately like 4 AWG copper on voltage drop. Aluminum still wins on cost and weight for feeders over about 100 A, which is why it dominates service entrance and large feeder work. For branch circuits under 50 A, copper's compactness and termination simplicity usually justify the premium. Either way, buy from a traceable mill source — our Cerro Wire inventory and the broader THHN collection carry the common branch and feeder sizes, and the PV wire vs. USE-2 vs. THHN guide explains which insulation types survive which environments.

    Common Voltage Drop Mistakes (Seen in the Field)

    1. Using one-way length without the round trip. The formula's "2" is not optional. Forgetting it makes every 120 V calc look twice as good as reality.
    2. Checking ampacity only. A 10 AWG run that passes 310.16 can still deliver 4–5% drop at 150 feet. Ampacity keeps insulation from melting; voltage drop keeps motors from cooking. Different failure modes, different checks.
    3. Sizing for breaker rating instead of actual load. Voltage drop depends on real operating current. A 20 A breaker feeding a 12 A actual load only drops voltage on 12 A — but if the load is continuous and may grow, design to the breaker.
    4. Ignoring the feeder share of the 5% budget. If the feeder to your subpanel already drops 2%, the branch circuit only has 3% left for a 5% total — the NEC's informational-note targets stack.
    5. Forgetting motor starting current. Locked-rotor current is 5–7× running current. A run that passes at full load can still sag hard enough at start to drop contactors or stall the compressor. Long motor feeds deserve extra margin or a soft start.
    6. Mixing up 208 V and 240 V. At 208 V the same absolute drop is a bigger percentage. Three-phase 208 V wye systems need their own check, not a 240 V assumption.

    When Voltage Drop Changes the Whole Design

    Sometimes the right answer isn't a bigger wire. Options worth pricing before you commit to 500 kcmil copper: move the panel or transformer closer to the load, step up to a higher distribution voltage, split the load across two smaller parallel runs (permitted at 1/0 and larger under 310.10(G) with strict symmetry rules), or — for solar and battery systems — locate the inverter at the array and run AC instead of long DC strings. Our NEC wire sizing guide for solar and generator installations walks through those system-level trade-offs, and the conduit fill chart tells you whether the upsized conductors still fit the raceway you planned. Once the wire is sized, match the overcurrent device using the breaker sizing 125% rule and verify the breaker itself in our circuit breaker inventory.

    Working the other side of a battery-based system? Long inverter-to-panel runs matter there too — pair this tool with the Battery Runtime Calculator and the Solar Panel Sizing Calculator to size the whole chain from array to load.

    Frequently Asked Questions

    Is the 3% voltage drop rule actually enforceable code?

    No. NEC 210.19(A) and 215.2(A)(1) express the 3%/5% figures in informational notes, which are recommendations, not mandates. However, many inspectors treat them as the de facto standard, equipment warranties often assume them, and some jurisdictions and project specifications adopt them as hard requirements. Designing to 3%/5% is the safe default everywhere.

    What K value should I use — 12.9 or 12.56 for copper?

    Both appear in the literature. K = 12.9 Ω·cmil/ft is the standard value at 75 °C conductor temperature, matching loaded conductors sized per the 75 °C column of 310.16. K = 12.56 applies at 25 °C. Using 12.9 is slightly conservative, which is the correct direction for design.

    Does voltage drop matter for solar PV DC strings?

    Yes — arguably more, because every volt dropped on the DC side is energy your inverter never converts. The solar industry commonly designs to 1.5–2% total DC drop. High string voltages (600–1000 V) make this easy; long low-voltage battery bank cables at 12–48 V are where DC drop becomes brutal.

    Why does my three-phase calculation use 1.732 instead of 2?

    In a balanced three-phase circuit, current returns through the other phases rather than a dedicated neutral, so the effective loop geometry changes. The √3 (1.732) multiplier applied to line-to-line voltage produces the correct percentage drop. Use it with the line-to-line system voltage (208, 240, or 480 V).

    Should I size for the motor's starting current?

    Not for the steady-state drop calculation — size for running current against 3%. But do verify that the sag during starting (5–7× running amps for a few seconds) won't drop out contactors, dim lights excessively, or stall the motor. Long motor feeders often get one extra size for exactly this reason.

    What if no single conductor gets me under 3%?

    Above roughly 750 kcmil the options are parallel conductor runs (1/0 AWG minimum, per NEC 310.10(G), with identical length, material, and termination), a higher system voltage, or relocating the source closer to the load. At that scale, have the design stamped by an engineer and get the conductor package quoted as a bundle.

    Related Products

    Shop the products mentioned in this guide and get everything you need for your project.

    Service Wire 10 AWG 1000V Solar PV Wire 500' Red - 10PV1000VREDX500

    Service Wire 10 AWG 1000V Solar PV Wire 500' Red - 10PV1000VREDX500

    Service Wire

    $337.00

    View Product
    Cerro Wire10 AWG 1/2kV Solar PV Wire 2500' Black - 10PV1000VX2500

    Cerro Wire10 AWG 1/2kV Solar PV Wire 2500' Black - 10PV1000VX2500

    Cerro Wire

    $1,575.00

    View Product
    Cerro Wire 8 AWG THHN/THWN-2 Stranded Copper Black 500'

    Cerro Wire 8 AWG THHN/THWN-2 Stranded Copper Black 500'

    Cerro Wire

    $347.00

    View Product

    Related PES Supply guides

    Need Help Sizing This?

    Our team can help you calculate loads, select the right equipment, and source everything from one PO.

    📞 (502) 790-0600

    Email Our Team
    Solar Panels Generators Batteries / ESS EV Chargers Circuit Breakers Charge Controllers

    One PO. One Invoice. Every Trade Covered.

    PES Supply is the distribution arm of PES Global Group — 50,000+ SKUs from 169 authorized brands, LTL freight shipping from Louisville, KY.

    Get a Quote
    Share: X f in @

    Related Articles

    NEC 310.16 Ampacity Table (2026): Copper & Aluminum by Gauge

    Oct 19, 2026

    EV Charger Breaker Sizing Chart (NEC 625)

    Oct 18, 2026

    Flex Duct CFM Chart: Every Size from 4″ to 18″ (2026 Guide)

    Oct 18, 2026
    MidNite Hawke's Bay vs Victron MPPT RS: 100A Face-Off

    MidNite Hawke's Bay vs Victron MPPT RS: 100A Face-Off

    Oct 17, 2026
    Friday Floor Scan: 5 Quiet Workhorses Worth a Second Look

    Friday Floor Scan: 5 Quiet Workhorses Worth a Second Look

    Oct 16, 2026
    This Week in Power & Solar: Factory Paper, Tandem Clocks, and the Tariff Floor (Oct 11)

    This Week in Power & Solar: Factory Paper, Tandem Clocks,...

    Oct 11, 2026
    Smart Load Management: EV Charging on a 100A Panel (No Service Upgrade)

    Smart Load Management: EV Charging on a 100A Panel (No Se...

    Oct 11, 2026
    LFP Battery Prices in 2026: The Floor Is Close — What to Buy Now

    LFP Battery Prices in 2026: The Floor Is Close — What to ...

    Oct 11, 2026
    How Wind Loads Affect Solar Panel Selection and Mounting

    How Wind Loads Affect Solar Panel Selection and Mounting

    Oct 10, 2026
    Solar Panel Fire Safety: What Installers and Building Owners Should Know

    Solar Panel Fire Safety: What Installers and Building Own...

    Oct 08, 2026
    New on the Floor: Five Project Kits That Just Landed

    New on the Floor: Five Project Kits That Just Landed

    Oct 03, 2026
    Winter Storm Season: Portable Generator Demand Climbs — What to Stock Now

    Winter Storm Season: Portable Generator Demand Climbs — W...

    Oct 02, 2026
    String Inverter vs Microinverter vs Power Optimizer: How the Architecture Changes

    String Inverter vs Microinverter vs Power Optimizer: How ...

    Oct 01, 2026
    Low-Light Solar Performance: Which Panels Produce More Energy on Cloudy Days?

    Low-Light Solar Performance: Which Panels Produce More En...

    Sep 27, 2026
    Solar Panel Pallets vs Containers: Which Buying Option Saves More Money?

    Solar Panel Pallets vs Containers: Which Buying Option Sa...

    Sep 19, 2026
    Solar Panels + EV Charging: How to Build an Energy-Efficient Home

    Solar Panels + EV Charging: How to Build an Energy-Effici...

    Sep 13, 2026
    Solar Panel Wholesale Pricing: What Installers Should Know in 2026

    Solar Panel Wholesale Pricing: What Installers Should Kno...

    Sep 08, 2026
    Solar Microgrids: How Communities Can Build More Resilient Energy Systems

    Solar Microgrids: How Communities Can Build More Resilien...

    Sep 07, 2026
    AI + Solar Energy: How Artificial Intelligence Is Changing Solar System Design

    AI + Solar Energy: How Artificial Intelligence Is Changin...

    Sep 05, 2026
    Volts to amps calculator hero — dark technical illustration, Portlandia Electric Supply

    Volts to Amps Conversion: How to Calculate Amps from Volt...

    Sep 04, 2026
    MWh to kWh conversion calculator hero — dark technical illustration, Portlandia Electric Supply

    MWh to kWh Conversion: Megawatt-Hours to Kilowatt-Hours C...

    Sep 04, 2026
    Watts to kilowatts calculator hero — dark technical illustration, Portlandia Electric Supply

    Watts to Kilowatts Conversion: W to kW Calculator + Chart...

    Sep 04, 2026
    kVA to amps calculator hero — transformer with glowing phase waveforms, Portlandia Electric Supply

    kVA to Amps Calculator: Single-Phase & Three-Phase Conver...

    Sep 04, 2026
    Milliamps to amps conversion calculator hero — dark technical illustration, Portlandia Electric Supply

    mA to Amps Conversion: Milliamps to Amps Calculator + Cha...

    Sep 04, 2026
    Wire ampacity calculator hero — copper cable gauges with glowing current, Portlandia Electric Supply

    Wire Ampacity Calculator (NEC 310.16): Copper & Aluminum ...

    Sep 04, 2026
    Generator sizing calculator hero — dark technical illustration, Portlandia Electric Supply

    Generator Sizing Calculator: Running + Starting Watts to ...

    Sep 04, 2026
    Solar panel sizing calculator hero — rooftop array with dimension lines, Portlandia Electric Supply

    Solar Panel Sizing Calculator: How Many Panels Does Your ...

    Sep 04, 2026
    Battery runtime calculator hero — dark technical illustration, Portlandia Electric Supply

    Battery Runtime Calculator: Ah to Hours With DoD & Invert...

    Sep 04, 2026
    Off-grid battery bank sizing calculator hero — stacked battery rack, Portlandia Electric Supply

    Off-Grid Battery Bank Sizing Calculator: kWh, Amp-Hours &...

    Sep 04, 2026
    Solar payback calculator hero — rooftop array with ascending savings curve, Portlandia Electric Supply

    Solar Payback Calculator: Payback Period & 25-Year Saving...

    Sep 04, 2026
    EV charger circuit calculator hero — charging cable and breaker panel, Portlandia Electric Supply

    EV Charger Circuit Calculator: Breaker & Wire Size per NE...

    Sep 04, 2026
    Service entrance load calculator hero — meter base and panel line art, Portlandia Electric Supply

    Service Entrance Load Calculator: NEC 220 Standard Method...

    Sep 04, 2026
    Conduit bending calculator hero — EMT offset bend with angle guides, Portlandia Electric Supply

    Conduit Bending Calculator: Offset Multiplier & Shrinkage...

    Sep 04, 2026
    LADWP and Investor-Owned Utility RFPs - A Bidder's Guide for Electrical and Renewable Equipment Supply

    LADWP and Investor-Owned Utility RFPs - A Bidder's Guide ...

    Sep 01, 2026
    Federal Contractor Buy-American Electrical Requirements - FAR 52.225 Compliance for Electrical, Solar, and Grid Equipment

    Federal Contractor Buy-American Electrical Requirements -...

    Sep 01, 2026
    State Cooperative Purchasing Programs for Electrical Equipment - Sourcewell, OMNIA, TIPS, NASPO ValuePoint

    State Cooperative Purchasing Programs for Electrical Equi...

    Sep 01, 2026
    Federal Solar RFP Response Template Library - Section L/M Compliance, Past Performance, and Bid Package Structure

    Federal Solar RFP Response Template Library - Section L/M...

    Sep 01, 2026
    GSA Schedule Roadmap for Electrical and Solar Suppliers - Multiple Award Schedule Application, Award, and Task Order Workflow

    GSA Schedule Roadmap for Electrical and Solar Suppliers -...

    Sep 01, 2026
    BABA Compliance for Electrical and Solar Equipment - 2 CFR 184, the 55% Rule, and How to Source Compliant Product

    BABA Compliance for Electrical and Solar Equipment - 2 CF...

    Sep 01, 2026
    HVAC Contractor Pallet Freight and LTL Guide: Hazmat Routing, DOT Compliance, and Landed Cost Economics

    HVAC Contractor Pallet Freight and LTL Guide: Hazmat Rout...

    Sep 01, 2026
    Commercial HVAC Refrigerant Compliance for Facility Managers: 40 CFR Part 82, Leak Repair Thresholds, and Penalty Avoidance

    Commercial HVAC Refrigerant Compliance for Facility Manag...

    Sep 01, 2026
    HVAC Service Tools Brand Selector: Fieldpiece vs Testo vs Fluke Digital Manifolds, Gauges, and Leak Detectors

    HVAC Service Tools Brand Selector: Fieldpiece vs Testo vs...

    Sep 01, 2026
    Refrigerant Recovery Equipment Buying Guide: Bacharach vs CPS vs Fieldpiece vs Yellow Jacket vs Appion

    Refrigerant Recovery Equipment Buying Guide: Bacharach vs...

    Sep 01, 2026
    PES Refrigerant Subscription Program: Recurring Pallet Delivery for HVAC Contractors

    PES Refrigerant Subscription Program: Recurring Pallet De...

    Sep 01, 2026
    EPA 608 Certification Guide: Type I, II, III, and Universal Testing Paths for HVAC Contractors

    EPA 608 Certification Guide: Type I, II, III, and Univers...

    Sep 01, 2026
    R-454B Transition Guide for HVAC Contractors: 2025 AIM Act, R-410A Phasedown, and Equipment Retrofits

    R-454B Transition Guide for HVAC Contractors: 2025 AIM Ac...

    Sep 01, 2026
    HVAC Contractor Refrigerant Buying Guide: R-410A, R-134a, R-22 Bulk Pricing & Hazmat Shipping

    HVAC Contractor Refrigerant Buying Guide: R-410A, R-134a,...

    Sep 01, 2026
    EPA Section 608 certification exam types and passing scores chart — PES Supply

    EPA Section 608 Certification: Complete Study Guide (Type...

    Aug 30, 2026

    R-410A Phase-Down 2026: What HVAC Contractors Need to Know

    Aug 29, 2026

    Get Price Drops & Product Releases

    Weekly digest for installers and project managers — price drops, new stock, NEC code updates.

    Portlandia Electric Supply