240V Wire Size Calculator: Breaker & Gauge Chart | PES

PES Supply, a PES Global Group Company
· 8 min read PES Engineering Desk — reviewed by a licensed master electrician
Open residential breaker panel with 240V double-pole breakers and copper feeders of different gauges

Table of Contents

    240V Wire Size Calculator: Breaker, Gauge, and Voltage Drop by Circuit Amps

    Reading time: ~8 min read

    📋 Key Takeaways

    • The classic 240V pairings: 20A → 12 AWG, 30A → 10 AWG, 40A → 8 AWG, 50A → 8 AWG (6 AWG for long runs), 60A → 6 AWG, all copper at the 75°C column of NEC 310.16.
    • Continuous loads change the math. EV chargers, water heaters, and anything running 3+ hours size at 125% of nameplate per NEC 210.19(A)(1)/210.20(A) — a 32A EVSE lands on a 40A breaker with 8 AWG copper.
    • Distance can beat ampacity. Past roughly 100–150 feet at 240V, voltage drop (NEC 210.19(A)(1) informational 3% branch-circuit guidance) forces a larger conductor than the ampacity table demands — our calculator checks both and returns the bigger wire.
    • Aluminum is legal and common for feeders and large 240V circuits — expect to go up about two AWG sizes versus copper and use listed AL-rated lugs with antioxidant.
    • The breaker protects the wire, not the appliance: never upsize a breaker to stop nuisance trips without rechecking conductor ampacity first.

    Every 240V circuit question — "what wire for a 30-amp dryer," "can I run 10/2 to a 50A range," "what gauge for a welder outlet 80 feet from the panel" — is really the same three-step problem: size the breaker to the load (with the 125% continuous multiplier where it applies), pick the smallest conductor whose 75°C ampacity covers the design current, then check that the run length doesn't push voltage drop past 3%. The calculator below runs all three steps and returns the breaker, the ampacity-minimum conductor, the voltage-drop-adjusted conductor, and the NEMA receptacle family that matches.

    Roughing in the circuit? Our electrical supplies collection has the breakers, THHN-2, NM-B, and receptacles to build it. If the load is an EV charger specifically, the EV charger circuit sizing guide covers the NEC 625 rules that stack on top of this math.

    240V Wire Size Calculator

    Amps = watts ÷ 240. A 7,680W EVSE draws 32A.

    Continuous loads design at 125% per NEC 210.20(A).

    Panel to receptacle, one way. Voltage drop checked at 3% (7.2V).

    Ampacities from NEC 310.16 at the 75°C column.

    Load / design current:

    Breaker (next standard size):

    Minimum conductor by ampacity (75°C):

    Conductor after voltage-drop check:

    Estimated voltage drop at full load:

    Typical receptacle:

    Sizing logic: continuous loads at 125% per NEC 210.19(A)(1)/210.20(A); breaker from the NEC 240.6(A) standard ratings; conductor from NEC 310.16 (75°C) with 240.4(D) small-conductor caps; voltage drop per the single-phase CM formula (CM = 2 × K × I × L ÷ VD, K = 12.9 Cu / 21.2 Al) against the NEC 210.19(A)(1) informational 3% branch-circuit guidance. Informational — the AHJ and equipment instructions govern.

    The Classic 240V Circuit Pairings (Copper, 75°C)

    For runs under 100 feet, ampacity — not distance — sets the wire size. These pairings cover nearly every residential 240V circuit:

    Breaker Min. copper wire Typical 240V loads Receptacle
    15 A 14 AWG Small window AC, water pump 6-15R
    20 A 12 AWG Window AC, small air compressor 6-20R
    30 A 10 AWG Electric dryer, tankless point-of-use heater 14-30R / 6-30R
    40 A 8 AWG Electric range, 7.7kW EVSE (32A continuous) 14-50R
    50 A 8 AWG Range, 9.6kW EVSE (40A continuous), RV pedestal 14-50R / 6-50R
    60 A 6 AWG Large tankless heater, subpanel feed, welder Hardwired
    80 A 4 AWG 19.2kW EVSE (64A continuous), large shop loads Hardwired
    100 A 3 AWG Subpanel feeder, whole-shop feed Hardwired

    Water heaters and EVSE are the two loads people most often mis-size, because both are continuous. A 4,500W water heater draws 18.8A but designs at 23.4A — 25A breaker minimum, 30A common, 10 AWG copper either way (the NEC 240.4(D) cap stops you at 30A). A 48A EVSE designs at 60A and wants 6 AWG copper on a 60A breaker.

    When Distance Takes Over: Voltage Drop

    NEC 210.19(A)(1) carries an informational note recommending no more than 3% voltage drop on a branch circuit and 5% total for feeder plus branch. At 240V, 3% is 7.2 volts. Ampacity tables assume the wire can dissipate heat; voltage drop cares about resistance over distance — so a 150-foot run to a barn or detached garage can require a size or two up even when the load is modest. The single-phase formula is CM = 2 × K × I × L ÷ VD, where K is 12.9 for copper and 21.2 for aluminum, I is the design current, and L is the one-way length. Our calculator runs it against every candidate conductor and reports the first size that satisfies both ampacity and drop. For a deeper treatment including three-phase runs and aluminum trade-offs, see the voltage drop calculator.

    Copper vs Aluminum at 240V

    Aluminum is the norm for feeders and increasingly common for big branch circuits: roughly two sizes up from copper (a 60A circuit on 6 AWG copper lands on 4 AWG aluminum) at 30–50% of the copper cost. The rules that matter: use AA-8000 series alloy, lugs marked AL or AL/CU, torque to the marked value with a calibrated tool, and apply antioxidant compound. Small aluminum branch circuits below 8 AWG are effectively obsolete for 240V appliance circuits — stick to copper there. Ampacities above come straight from the 75°C column; if the conduit run is hot or crowded, run those conditions through the ampacity chart before committing.

    Frequently Asked Questions

    What size wire do I need for a 30-amp 240V circuit?

    10 AWG copper (10/2 NM-B for a dryer) or 8 AWG aluminum. NEC 310.16 rates 10 AWG copper at 35A in the 75°C column, and NEC 240.4(D) caps it at 30A of overcurrent protection. For runs past about 120 feet at a full 30A load, step up to 8 AWG copper to hold voltage drop near the 3% guidance.

    What size wire for a 50-amp 240V circuit?

    8 AWG copper or 6 AWG aluminum for runs under 100 feet. A 50A circuit feeding a continuous load (like a 40A EVSE) designs at 50A exactly, and 8 AWG copper's 50A ampacity at 75°C covers it with no margin — long runs or hot conduits push you to 6 AWG copper. Use a 14-50R receptacle when a neutral is present, 6-50R for straight 240V loads like welders.

    Can I use 12-gauge wire on a 240V circuit?

    Yes — on a 20A breaker. Voltage has nothing to do with wire size; current does. 12 AWG copper on 240V is exactly the same 20A-max conductor it is on 120V, per NEC 240.4(D). You need a double-pole 20A breaker and typically a 6-20R receptacle. The mistake to avoid is assuming 240V loads need bigger wire automatically: a 3,000W 240V heater draws only 12.5A and runs fine on 12 AWG.

    How far can I run 10-gauge wire at 240V before voltage drop matters?

    About 130 feet at a full 30A load before drop exceeds 3% (7.2V). At 20A on the same 10 AWG copper you get roughly 195 feet; at 24A continuous (design 30A) about 130 feet. The rule of thumb: every doubling of distance doubles the drop, and dropping the load current proportionally extends the acceptable distance. Longer runs to outbuildings usually land on 8 or 6 AWG.

    Do 240V circuits need a neutral wire?

    Only if the appliance uses 120V internally. Straight 240V loads — baseboard heaters, water heaters, welders, most EVSE — need two hots plus ground only. Appliances with timers, lights, or 120V control boards (dryers, ranges) need the neutral, which is why they use 14-30R and 14-50R receptacles with four conductors. Since NEC 250.140, new dryer and range circuits must be four-wire; the old three-wire exception applies to existing installations only.

    Building a 240V Circuit?

    PES Supply stocks double-pole breakers, NM-B and THHN-2 by the foot, NEMA receptacles, and disconnects from 169 authorized brands. Send the load list — we'll quote the complete circuit at contractor pricing.

    Shop Electrical Supplies Contact Us for Bulk Pricing

    Related Resources

    Need Help Sizing This?

    Our team can help you calculate loads, select the right equipment, and source everything from one PO.

    📞 (502) 790-0600

    Email Our Team
    Solar Panels Generators Batteries / ESS EV Chargers Circuit Breakers Charge Controllers

    One PO. One Invoice. Every Trade Covered.

    PES Supply is the distribution arm of PES Global Group — 50,000+ SKUs from 169 authorized brands, LTL freight shipping from Louisville, KY.

    Get a Quote
    Share: X f in @

    Related Articles

    White residential propane tank beside a standby generator on a concrete pad in a suburban backyard

    Propane Tank Sizing for Generators: Calculator | PES

    Sep 19, 2026
    Residential electric meter on an exterior wall beside the service entrance conduit of a suburban home

    Power Consumption Calculator: kWh & Cost | PES

    Sep 19, 2026
    Galvanized round HVAC ducts and flex duct branching across a residential attic with foil insulation

    Duct Size Calculator: CFM Chart by Room & Ton | PES

    Sep 19, 2026
    Electrician measuring current with a clamp meter on a copper conductor inside a residential breaker panel

    Amps to Watts Calculator: 120V, 240V & 12V | PES

    Sep 19, 2026
    Rooftop solar array with conduit down to an open main service panel showing the backfed PV breaker

    Solar 120% Rule Calculator: Max PV Breaker | PES

    Sep 19, 2026
    Commercial standby generator on a concrete pad with a wall-mounted automatic transfer switch

    kVA to kW Calculator: Power Factor Converter | PES

    Sep 19, 2026
    Electrician pulling THHN copper conductors into EMT conduit on a hot commercial rooftop

    Ampacity Derating Calculator: NEC 310.16 & Heat | PES

    Sep 19, 2026
    Solar charge controller mounted on utility-room wall with battery bank cables

    Solar Charge Controller Sizing Calculator | PES

    Sep 19, 2026
    Residential rooftop solar array with series-string wiring and aluminum racking

    Solar String Sizing: Max Panels in Series | PES

    Sep 19, 2026
    Rooftop air-conditioning condenser unit with electrical disconnect and conduit whip

    MCA vs MOCP: AC Circuit Sizing Calculator | PES

    Sep 19, 2026
    Open residential breaker panel with labeled double-pole breakers and copper feeders

    Breaker Size Calculator: 125% Rule & Wire Chart | PES

    Sep 19, 2026
    Off-grid hybrid inverter with battery rack and conduit runs in a utility room

    Off-Grid Inverter Sizing: Continuous, Surge & Battery | PES

    Sep 18, 2026
    Electrician's hand holding a circuit breaker in front of an open load center

    Breaker Compatibility Chart: QO vs BR vs QP Panels | PES

    Sep 18, 2026
    Row of residential rooftop solar panels in soft daylight, close-up on glass cells

    Solar Panel Wattage Chart: 400W vs 450W vs 500W+ | PES

    Sep 18, 2026
    Automatic transfer switch with thick copper conductors next to breaker panel

    Transfer Switch Wire Sizing: Ampacity Chart by kW | PES

    Sep 18, 2026
    Torque screwdriver tightening a terminal lug on a copper conductor in a panel

    Lug Torque Chart: NEC 110.14 Terminal Tightness by Size &...

    Sep 18, 2026
    Electrical subpanel with feeder cable and neatly dressed branch circuits

    Subpanel Sizing Guide: Feeder Size, Spaces & Load Calc | PES

    Sep 18, 2026
    Residential rooftop solar installation at golden hour with installer tools nearby

    Solar ROI Calculator: Payback, ITC & 25-Year Savings by S...

    Sep 18, 2026
    Standby generator on concrete pad with automatic transfer switch on house wall

    Transfer Switch Sizing Guide: Amps, Circuits & ATS vs Man...

    Sep 18, 2026
    Standby generator beside a residential propane tank and natural gas line

    Standby Generator Fuel Consumption Chart: NG, Propane & D...

    Sep 17, 2026
    Home battery storage wall unit in a garage powering household circuits

    Solar Battery Backup Runtime Calculator: Hours by Load & ...

    Sep 17, 2026
    Service entrance mast and meter base on a residential exterior wall

    Service Entrance Cable Size Calculator: 100A/200A/400A Se...

    Sep 17, 2026
    Green-insulated copper grounding conductors bonded to a ground bar in a panel

    Ground Wire Size Chart: NEC 250.122 EGC Sizing by Breaker...

    Sep 17, 2026
    Thick red and black battery cables with crimped lugs on a battery bank rack

    Battery Cable Size Chart: 12V/24V/48V Inverter & Bank Cab...

    Sep 17, 2026
    Level 2 EV charger wall-mounted in a residential garage with dedicated circuit

    EV Charger Circuit Sizing: NEC 625 Breaker, Wire & Load C...

    Sep 17, 2026
    PV wire runs with MC4 connectors under a rooftop solar array

    Solar Wire Size Calculator: PV Wire, Ampacity & Voltage D...

    Sep 17, 2026
    Slotted wire duct and cable tray with organized conductors in a control panel

    Wire Duct & Cable Tray Sizing Guide: Wireway Fill, Types ...

    Sep 17, 2026
    Residential main service panel with digital load meter and labeled circuit directory

    Electrical Load Calculation: NEC 220 Demand Factors for S...

    Sep 16, 2026
    Dry-type electrical transformer with conduit connections in a commercial electrical room

    Transformer Sizing Calculator: kVA, Load & Voltage Select...

    Sep 16, 2026
    Open electrical junction box with wire nuts and folded conductors, work in progress

    Box Fill Calculator: NEC 314.16 Conductor & Device Allowa...

    Sep 16, 2026
    EMT conduit runs with multiple insulated conductors pulled through, exposed ceiling

    Conduit Fill Calculator: NEC Chapter 9 Tables for EMT, PV...

    Sep 16, 2026
    Whole-home standby generator on a pad beside a house with transfer switch

    Generator Sizing Calculator: Running Watts, Starting Watt...

    Sep 16, 2026
    Full residential rooftop solar array with inverter and meter on exterior wall

    Solar System Sizing Calculator: From kWh Usage to Array S...

    Sep 16, 2026
    Industrial electric motor with motor starter and nameplate in a mechanical room

    Motor FLA Chart: NEC 430.250 Full-Load Amps, Breaker & Wi...

    Sep 16, 2026
    Copper ground rod with clamp and bare grounding electrode conductor at a foundation

    Grounding & Earthing Guide: NEC 250, GEC Sizing Chart & G...

    Sep 16, 2026
    Close-up of stripped copper wire ends in several AWG gauges side by side

    AWG Wire Gauge Chart: Diameter, Resistance, Ampacity & Ap...

    Sep 16, 2026
    Server-rack lithium battery bank with busbars in a clean utility room

    Battery Bank Sizing Calculator: kWh, Days of Autonomy & D...

    Sep 16, 2026
    Assorted THHN copper wire gauges in colored insulation laid out on a workbench

    Wire Size by Amps: Ampacity Chart & Breaker Matching Guid...

    Sep 16, 2026
    Long run of copper conductors in conduit with multimeter measuring voltage on site

    Voltage Drop Calculator: Wire Size, Distance & NEC 3% Rul...

    Sep 16, 2026
    High-efficiency monocrystalline solar panels on a residential rooftop at golden hour

    Most Efficient Solar Panels of 2026: A Buyer's Guide for ...

    Aug 23, 2026
    Enphase Brand Guide: IQ7/IQ8 Microinverters, IQ Battery, and Installer Ecosystem

    Enphase Brand Guide: IQ7/IQ8 Microinverters, IQ Battery, ...

    Aug 12, 2026
    Wallbox home EV wall charger — PES Supply brand guide

    Wallbox Chargers: Brand Guide for Smart EV Charging

    Jul 06, 2026
    Victron Energy marine-blue charge controller and inverter-charger — PES Supply brand guide

    Victron Energy Brand Guide: SmartSolar, BlueSolar, MultiP...

    Jul 01, 2026
    Unirac flat-roof ballasted racking system — PES Supply brand guide

    Unirac Brand Guide: SolarMount, Flashloc, and UL 3741-Com...

    Jun 30, 2026
    Trojan Battery deep-cycle flooded batteries on rack — PES Supply brand guide

    Trojan Battery Brand Guide: Deep-Cycle FLA, AGM, Gel & LFP

    Jun 29, 2026
    Trina Solar commercial rooftop solar panel array — PES Supply brand guide

    Trina Solar Brand Guide: Vertex Series, 210mm Cells & Dea...

    Jun 24, 2026
    Sungrow residential string inverter on exterior wall — PES Supply brand guide

    Sungrow: Residential, Commercial, and Hybrid Inverter Bra...

    Jun 23, 2026
    sonnen wall-mounted home battery system — PES Supply brand guide

    Sonnen Brand Guide: All-in-One LFP Battery Systems

    Jun 22, 2026
    SolarEdge power optimizers behind rooftop panels — PES Supply brand guide

    SolarEdge Technologies: Power Optimizer and Inverter Bran...

    Jun 17, 2026

    Get Price Drops & Product Releases

    Weekly digest for installers and project managers — price drops, new stock, NEC code updates.

    PES Supply, a PES Global Group Company