Motor FLA Chart: NEC 430.250 Full-Load Amps, Breaker & Wire Sizing
Reading time: ~11 min read
📋 Key Takeaways
- Use the NEC tables — 430.248 for single-phase, 430.250 for three-phase — not the motor nameplate, for conductor and breaker sizing.
- Branch-circuit conductors are sized at 125% of table FLA per NEC 430.22.
- Inverse-time breakers are sized at up to 250% of table FLA per 430.52(C)(1), rounded up to the next standard size when needed.
- Overload heaters are sized from the motor nameplate FLA per 430.32 — this is the one place the nameplate rules.
- The breaker protects the circuit from shorts and ground faults; the overloads protect the motor. Oversizing the breaker to stop nuisance trips is not the fix.
Motor circuits break the rules electricians learn for everything else: the breaker can be several times larger than the wire's ampacity, the conductor is sized from a table value instead of the nameplate, and the same HP motor draws wildly different current at 208V versus 460V. This reference gives you the full-load amp (FLA) tables from NEC 430.248 and 430.250, the wire and breaker sizing math from 430.22 and 430.52, starter and overload selection notes, and an interactive calculator that does the whole branch circuit in one pass. When you're ready to buy, our breakers, contactors, and motor-rated disconnects are in stock at PES Supply.
Why the NEC Uses Table FLA Instead of the Nameplate
Every motor branch-circuit calculation — conductors, breaker or fuse, and disconnect — starts from the FLA values in NEC tables 430.247 through 430.250, per 430.6(A)(1). The nameplate current is used only for sizing the overload protection (430.32) and for motors not covered by the tables.
Why? The tables standardize on typical motor efficiency and power factor, so a replacement motor that draws more (or less) than the original doesn't invalidate the circuit design. The nameplate describes one specific motor; the circuit has to outlive it.
Single-Phase Motor FLA Chart (NEC Table 430.248)
Full-load currents in amperes for single-phase AC motors. Values below are the common 115V and 230V ratings:
| HP | 115V | 200V | 208V | 230V |
|---|---|---|---|---|
| 1/2 | 9.8 | 5.6 | 5.4 | 4.9 |
| 3/4 | 13.8 | 7.9 | 7.6 | 6.9 |
| 1 | 16 | 9.2 | 8.8 | 8 |
| 1½ | 20 | 11.5 | 11 | 10 |
| 2 | 24 | 13.8 | 13.2 | 12 |
| 3 | 34 | 19.6 | 18.7 | 17 |
| 5 | 56 | 32.2 | 30.8 | 28 |
| 7½ | 80 | 46 | 44 | 40 |
| 10 | 100 | 57.5 | 55 | 50 |
Note: Table 430.248 stops at 10 HP for single-phase. Larger single-phase motors exist but are increasingly rare — above 10 HP, spec three-phase wherever utility service allows.
Three-Phase Motor FLA Chart (NEC Table 430.250)
Full-load currents in amperes for three-phase squirrel-cage and wound-rotor induction motors, standard Design B efficiency class:
| HP | 208V | 230V | 460V |
|---|---|---|---|
| 1/2 | 2.4 | 2.2 | 1.1 |
| 3/4 | 3.5 | 3.2 | 1.6 |
| 1 | 4.6 | 4.2 | 2.1 |
| 1½ | 6.6 | 6.0 | 3.0 |
| 2 | 7.5 | 6.8 | 3.4 |
| 3 | 10.6 | 9.6 | 4.8 |
| 5 | 16.7 | 15.2 | 7.6 |
| 7½ | 24.2 | 22 | 11 |
| 10 | 30.8 | 28 | 14 |
| 15 | 46.2 | 42 | 21 |
| 20 | 59.4 | 54 | 27 |
| 25 | 74.8 | 68 | 34 |
| 30 | 88 | 80 | 40 |
| 40 | 114 | 104 | 52 |
| 50 | 143 | 130 | 65 |
| 60 | 169 | 154 | 77 |
| 75 | 211 | 192 | 96 |
| 100 | 273 | 248 | 124 |
Two warnings the tables can't print big enough:
- 208V is not 230V. A 10 HP motor that draws 28A at 230V draws 30.8A at 208V — about 10% more. Sizing a 208V feeder off the 230V column is a quiet way to cook a conductor over years of service.
- Synchronous motors and high-efficiency (Design E) motors have different values. Design E motors draw lower FLA but much higher locked-rotor current, which can force breaker size-ups. Check 430.32 and the drive/starter manufacturer's data before substituting.
Wire Sizing: NEC 430.22 (125% Rule)
Conductors supplying a single continuous-duty motor must have an ampacity of at least 125% of the table FLA. Not the nameplate, not the breaker rating — 125% of the 430.248/430.250 value, then look up the conductor in Table 310.16.
Worked example — 10 HP, 230V, three-phase:
- Table 430.250 FLA = 28A.
- 125% × 28A = 35A minimum conductor ampacity.
- Table 310.16 at 75°C (THHN/THWN-2, 75°C terminations): 10 AWG copper = 35A. Use 10 AWG.
For motors on VFDs, 430.122 bumps the conductor to 125% of the drive's rated input current, which is often higher than motor FLA — read the drive nameplate, not the motor's. And remember the termination rule from 110.14(C): circuits 100A and under generally land on 75°C terminations, so you can't take credit for the 90°C column even with THHN-2 in the pipe.
Breaker Sizing: NEC 430.52 (250% Rule)
The branch-circuit short-circuit and ground-fault protective device is not overload protection — it only has to let the motor start without tripping while clearing faults fast. Table 430.52 sets maximum ratings by device type:
| Device Type | Max % of FLA (squirrel-cage, non-Design E) |
|---|---|
| Non-time-delay fuse | 300% |
| Dual-element (time-delay) fuse | 175% |
| Instantaneous-trip breaker | 800% |
| Inverse-time breaker (standard thermal-magnetic) | 250% |
Rules of application per 430.52(C)(1):
- Round up, not down. If 250% of FLA doesn't land on a standard rating from 240.6(A), Exception 1 lets you go to the next higher standard size. For our 10 HP example: 250% × 28A = 70A exactly — a 70A breaker. For a 7½ HP at 230V three-phase: 250% × 22A = 55A, which isn't standard, so a 60A breaker.
- Still nuisance-tripping on start? 430.52(C)(1) Exception 2 permits going above the table percentage where starting current demands it (up to 400% for inverse-time breakers on motors 100A FLA or less). Document it — the inspector will ask.
- The wire stays small on purpose. That 60A breaker feeding 10 AWG wire is legal and correct for a motor circuit because the overload relay in the starter carries the overload-protection duty (430.32). This is the single most-misunderstood thing in Article 430.
Starter and Overload Selection Notes
Once the circuit is sized, the starter has to match the motor, and the overloads have to match the nameplate:
- NEMA starter sizes: Size 00 to about 1 HP at 230V three-phase; Size 0 to 3 HP; Size 1 to 10 HP; Size 2 to 25 HP; Size 3 to 50 HP at 230V — double the HP ratings at 460V. Always confirm against the manufacturer's table for your exact voltage and duty.
- Overload heaters per 430.32(A)(1): 125% of nameplate FLA for motors with a service factor of 1.15 or greater, or marked temperature rise of 40°C or less; 115% for everything else. Start at the lower setting and only step up per 430.32(C) if the motor trips before reaching operating speed.
- Locked-rotor current: verify the starter and breaker can carry 6–8× FLA during acceleration. Across-the-line starting a big motor on a marginal service is a voltage-sag complaint waiting to happen — that conversation is where soft starters and VFDs earn their keep.
- Disconnects (430.109): motor-circuit switches must be HP-rated at the applied voltage. A snap switch or general-use switch on a motor load is a red tag and an arc-flash hazard.
Interactive Motor Circuit Sizing Calculator
Pick horsepower, phase, and voltage. The calculator returns NEC table FLA, minimum copper conductor at 125% (75°C column of Table 310.16), and the maximum inverse-time breaker at 250% rounded to the next standard size.
Reference only, per NEC 430.248/430.250 FLA, 430.22 conductor at 125%, 430.52 inverse-time breaker at 250% (next standard size up). Single-phase table limited to 10 HP. Verify against the adopted NEC edition, nameplate, and your AHJ. Overloads: 125%/115% of nameplate FLA per 430.32.
Frequently Asked Questions
Why is my motor breaker bigger than the wire allows?
Because it's supposed to be. The inverse-time breaker at up to 250% of FLA only protects against short circuits and ground faults; the starter's overload relay, set from the nameplate FLA per 430.32, protects the motor and the conductors from overload. Article 430 deliberately separates those two jobs.
Do I size motor wire from the nameplate amps?
No. NEC 430.6(A)(1) requires conductors, breakers, and disconnects to be sized from the FLA tables (430.248/430.250). The nameplate current is used only for overload heater selection per 430.32 and for motors the tables don't cover.
What size breaker do I need for a 10 HP, 230V, 3-phase motor?
Table 430.250 FLA is 28A. At 250% per 430.52, that's exactly 70A — a standard 240.6 size, so a 70A inverse-time breaker. Conductors at 125% need 35A ampacity, so 10 AWG copper THHN/THWN-2.
Why does 208V matter so much for motor sizing?
Motors are constant-horsepower devices: drop the voltage and the current rises to deliver the same power. NEC Table 430.250 shows about 10% higher FLA at 208V than at 230V. Sizing conductors or starters off the 230V column for a 208V system undersizes the whole branch circuit.
Can I use a higher breaker if the motor won't start?
Yes, within limits. NEC 430.52(C)(1) Exception 2 allows an inverse-time breaker above 250% — up to 400% for motors with FLA of 100A or less — where starting current makes the table value impractical. Verify locked-rotor current, document the engineering basis, and expect the AHJ to ask for it.