Service Entrance Cable Size Calculator: 100A/200A/400A Services | PES

PES Supply, a PES Global Group Company
· 9 min read PES Engineering Desk — reviewed by a licensed master electrician
Service entrance mast and meter base on a residential exterior wall

Table of Contents

    Service Entrance Cable Size Calculator: 100A, 200A & 400A Services

    Reading time: ~10 min read

    📋 Key Takeaways

    • For a dwelling service or feeder carrying the entire load, NEC 310.12 lets you size conductors at 83% of the service rating — a 200A dwelling service needs wire rated for just 166A: 2/0 Cu or 4/0 Al.
    • Non-dwelling and non-full-load circuits size straight off Table 310.16 (75°C column for these sizes): a 200A commercial service is 3/0 Cu or 250 kcmil Al — a full size heavier.
    • The 200A residential standard answer: 2/0-2/0-2/0-4 AWG Al SER is out of code for 310.12 dwellings (4/0 is the minimum neutral/EGC math aside) — use 4/0-4/0-4/0-2/0 Al SER or 2/0 Cu THHN in conduit.
    • SER is the default for interior runs to the panel; USE-2/RHW for underground laterals; THHN/XHHW-2 in conduit when the AHJ or job spec requires raceway.
    • Long service runs (200+ ft to a detached structure or ranch panel) need a voltage-drop check — 3% on the service can push you one or two sizes past the ampacity answer.

    "What size wire for a 200-amp service?" is the single most-asked wire question in the trade, and it has two correct answers depending on which NEC table applies. For dwelling units, NEC 310.12 (the old 310.15(B)(7)) recognizes that residential services never actually carry their full rating and lets you size at 83% — that's why 2/0 copper and 4/0 aluminum are everywhere. Everything else sizes off Table 310.16 at the 75°C column. The calculator below handles both paths: pick the service rating, material, and method, and it returns the conductor size, then runs a voltage-drop check if you give it a one-way run length.

    Building a service package? Our electrical supplies collection stocks SER, USE-2, THHN/XHHW-2, meter bases, and panels from 169 authorized brands — and our generators collection pairs naturally with transfer equipment for backup-ready services.

    Service Entrance Cable Calculator

    310.12 applies only when the service/feeder carries the entire dwelling load.

    Voltage-drop check at full service rating, 240V single-phase.

    Required conductor: —

    Typical cable assembly: —

    Voltage drop check: —

    Dwelling sizes per NEC Table 310.12 (2020/2023); standard sizes per Table 310.16 at 75°C (terminals at these ratings are 75°C listed per 110.14(C)). Voltage drop computed as 2·K·I·L/cmil with K=12.9 (Cu) / 21.2 (Al) at 240V single-phase against a 3% target — informational only; the NEC treats service VD as a design recommendation, not a hard limit. Final sizing belongs to the NEC 220 load calculation and the AHJ.

    Service Entrance Size Chart (Dwelling vs. Standard)

    The two code paths side by side. The dwelling column assumes NEC 310.12 applies — service or feeder carries the entire load of a dwelling unit. Anything else (commercial, detached-building feeders that don't carry the whole dwelling, services feeding multiple units) uses the standard column:

    Service rating Dwelling 310.12 — Cu Dwelling 310.12 — Al Standard 310.16 (75°C) — Cu Standard 310.16 — Al
    100 A 4 AWG 2 AWG 3 AWG 1 AWG
    125 A 2 AWG 1/0 AWG 1/0 AWG 2/0 AWG
    150 A 1 AWG 2/0 AWG 1/0 AWG 3/0 AWG
    200 A 2/0 AWG 4/0 AWG 3/0 AWG 250 kcmil
    225 A 3/0 AWG 250 kcmil 4/0 AWG 300 kcmil
    320 A (400A class) 350 kcmil 500 kcmil 400 kcmil 600 kcmil
    400 A 400 kcmil 600 kcmil 600 kcmil 800 kcmil (or parallel 250 kcmil Al)

    The 400A row deserves a footnote: most residential "400A" services are actually 320A continuous-class meter bases feeding two 200A panels, which is why 350 kcmil Cu / 500 kcmil Al is the honest dwelling answer. True 400A services at the 75°C column land at 600 kcmil Cu or parallel runs — at which point most shops run parallel 250 kcmil Al or a CT cabinet with utility-approved conductors.

    The 83% Rule (NEC 310.12), Explained Without Folklore

    310.12 isn't a discount and it isn't optional voodoo — it's the NEC formalizing diversity. Dwelling loads are wildly non-coincident: the range, dryer, AC, and water heater never peak together. So for a service or feeder carrying the entire load of a dwelling unit (one-family, two-family, or an individual unit of a multifamily), the conductors only need an ampacity of 83% of the service rating. 200 × 0.83 = 166A, and 2/0 Cu at 75°C (175A) or 4/0 Al (180A) covers it.

    Where contractors get burned is applying 310.12 to things it doesn't cover:

    • Subpanel feeders that carry only part of the dwelling load — a 100A feeder to a garage subpanel fed from the main panel is not the entire dwelling load; it's straight 310.16 (though 2023 NEC added 310.12(B) covering feeders serving the entire load of a dwelling unit, e.g., a downstream main panel after a service disconnect).
    • Commercial and mixed-use services — no 83%, ever. 310.16 at the termination column.
    • Services with no capacity margin — the conductor must still carry the calculated NEC 220 load; if the load calc exceeds 83% of rating, the calc governs.

    SER vs. SEU vs. THHN vs. USE-2: Picking the Assembly

    Once the size is settled, the assembly question is mostly about the route:

    • SER (service entrance, round): the residential default overhead/interior answer — two or three insulated conductors plus a bare neutral/ground in an overall jacket, sunlight-resistant, run exposed or in raceway. 4/0-4/0-4/0-2/0 Al SER is the classic 200A dwelling assembly.
    • SEU (U-style): flat twin-hot with concentric neutral — older stock, still listed, less common on new work.
    • THHN/XHHW-2 in conduit: required when the AHJ wants raceway end-to-end, in commercial work, and whenever you want the neutral insulated and full-size. Costs more in labor, wins on flexibility and repairability.
    • USE-2/RHW direct burial: the underground lateral answer — single conductors, no overall assembly, sunlight-resistant and rated for direct earth burial. Triplex/quadplex URD assemblies are the utility-side cousin.

    One trap: NM-B and UF are not service-entrance wiring methods (338.10/340.10 restrictions aside, 338.12 limits SE use), and SER used indoors must still respect the 60°C NM-style rules only when the AHJ treats it as a cable assembly — most read SER at 75°C because the conductors inside are XHHW-2. Ask before you pull.

    Voltage Drop on Long Service Runs

    Rural lots, detached shops, and deep-set panels turn an ampacity answer into a voltage-drop problem fast. The math at 240V single-phase: VD = 2·K·I·L ÷ cmil, with K=12.9 for copper and 21.2 for aluminum. A 200A service run 300 feet on 4/0 Al drops about 15.4V — 6.4%, double the 3% design target — and the fix is 300 kcmil Al or stepping to copper. The NEC's 3% figures are informational notes for services (design practice, not a hard limit), but 210.19/215.2 make 3% branch/feeder numbers enforceable-adjacent in many jurisdictions, and every inspector has seen a dimming-light callback from a skinny lateral. Run the calculator above with your actual length before ordering wire; the cost of one size up is trivial next to a re-pull.

    Frequently Asked Questions

    What size wire do I need for a 200-amp service?

    For a dwelling under NEC 310.12 (the 83% rule): 2/0 AWG copper or 4/0 AWG aluminum — typically installed as 4/0-4/0-4/0-2/0 Al SER or 2/0 Cu THHN in conduit. For non-dwelling services sized from Table 310.16 at 75°C: 3/0 AWG copper or 250 kcmil aluminum. Long runs over ~200 ft should also be checked for voltage drop, which can push the size up regardless of the table answer.

    What size wire for a 100-amp service?

    Dwelling sizing per NEC 310.12: 4 AWG copper or 2 AWG aluminum — the common assembly is 2-2-2-4 Al SER. Standard Table 310.16 sizing at 75°C for non-dwelling applications: 3 AWG copper or 1 AWG aluminum. Note that some AHJs and older stock conventions still quote 2 AWG Cu for 100A — that's the 310.12 answer and applies only to full dwelling loads.

    What is the 83% rule for service entrance cable?

    NEC 310.12 allows conductors for a service or feeder carrying the entire load of a dwelling unit to be sized at 83% of the service rating, recognizing residential load diversity. A 200A dwelling service therefore needs conductors rated for 166A (2/0 Cu or 4/0 Al), not 200A. It does not apply to commercial services, partial-load subpanel feeders, or any case where the calculated load exceeds 83% of the rating.

    Can I use aluminum wire for a service entrance?

    Yes — aluminum (AA-8000 series) is the standard residential service-entrance material and what most SER and URD cable is made of. Use 75°C-rated terminations, wire-brush and apply antioxidant compound per manufacturer instructions, torque lugs to spec with a calibrated tool, and never use aluminum smaller than the minimums in 230.31/338.10. The two-sizes-larger penalty versus copper is already reflected in Tables 310.12 and 310.16.

    What size wire for a 400-amp residential service?

    Most residential "400A" services are 320A-class meter bases feeding two 200A panels. Under NEC 310.12 for the full dwelling load, the 320/400A row calls for 350 kcmil copper or 500 kcmil aluminum; true 400A sizing from Table 310.16 at 75°C is 600 kcmil copper or parallel aluminum. Because single conductors that large are unwieldy, many installs use parallel 250 kcmil Al runs or a CT cabinet — coordinate with the utility and AHJ before ordering.

    Quoting a Service Change or New Service?

    PES Supply stocks SER, USE-2, THHN/XHHW-2, meter bases, and panels from 169 authorized brands. Send the one-line and run lengths — we'll quote the complete service package at contractor pricing.

    Shop Electrical Supplies Contact Us for Bulk Pricing

    Related Resources

    Related PES Supply guides

    Need Help Sizing This?

    Our team can help you calculate loads, select the right equipment, and source everything from one PO.

    📞 (502) 790-0600

    Email Our Team
    Solar Panels Generators Batteries / ESS EV Chargers Circuit Breakers Charge Controllers

    One PO. One Invoice. Every Trade Covered.

    PES Supply is the distribution arm of PES Global Group — 50,000+ SKUs from 169 authorized brands, LTL freight shipping from Louisville, KY.

    Get a Quote
    Share: X f in @

    Related Articles

    Generac 22kW vs Kohler 20kW Standby Generator: Real Specs

    Generac 22kW vs Kohler 20kW Standby Generator: Real Specs

    Oct 19, 2026
    Best Solar Panels for Cloudy Climates: What Actually Matters

    Best Solar Panels for Cloudy Climates: What Actually Matters

    Oct 02, 2026
    Pallet of boxed solar panels in shrink wrap on a warehouse floor with a liftgate box truck behind

    Solar Panel Pallet Cost, Delivered: $/W Math | PES

    Sep 23, 2026
    Commercial flat-roof solar array with copper grounding lugs bonding aluminum racking rails

    Commercial Solar Grounding BOM: NEC 690.43 | PES

    Sep 23, 2026
    All-black solar panels on a residential shingle rooftop in late afternoon sunlight

    Aptos DNA 460W Panel: Specs, Price & Family | PES

    Sep 23, 2026
    Residential standby generator on a concrete pad beside a brick home with conduit to a wall-mounted transfer switch

    Briggs PowerProtect 13kW Shell + Symphony II ATS | PES

    Sep 23, 2026
    Full wooden pallet stacked with boxed solar panels in shrink film on a warehouse floor with a flatbed liftgate truck behind

    Buying Solar Panels by the Pallet: Pro Guide | PES

    Sep 23, 2026
    Wall-mounted hybrid solar inverter in a tidy residential utility room with metal conduit, red and black battery cables and a subpanel

    Sol-Ark vs GoodWe Hybrid Inverter Guide | PES

    Sep 23, 2026
    Two modern wall-mounted home battery storage units side by side on a clean residential garage wall with conduit and a disconnect

    EG4 Battery vs Tesla Powerwall 3: Honest Comparison | PES

    Sep 23, 2026
    Caribbean-style home in Puerto Rico with a rooftop solar array and a wall-mounted home battery, palm trees and bright sun

    Puerto Rico Solar + Battery Resilience Guide | PES

    Sep 23, 2026
    All-black residential rooftop solar panels with a uniform busbar-free surface on a shingle roof

    AIKO Solar Panels: Price, Specs & ABC Technology | PES

    Sep 23, 2026
    Commercial ground-mount bifacial solar array on light gravel under a clear sky

    Bila Solar AA-530US: Domestic Content Panels & ITC | PES

    Sep 23, 2026
    Gloved hand clamping a split-core current transformer around a conductor inside an open electrical panel

    Accu-CT Split-Core Sensors Explained: 333mV CTs | PES

    Sep 23, 2026
    Floor-standing home battery storage cabinet beside a wall-mounted hybrid inverter in a residential garage

    Big Battery NEXUS 15kWh Explained: Specs & Scaling | PES

    Sep 23, 2026
    Through-the-wall PTAC air conditioner installed on a hotel guestroom wall beneath a large window

    Amana PTAC Sizing Guide: 7,000–15,000 BTU Ladder | PES

    Sep 23, 2026
    Residential standby generator on a composite pad beside a suburban home with an electrician work van in the driveway

    Champion aXis Generator Guide: 8.5kW, 14kW & 22kW | PES

    Sep 23, 2026
    Air-cooled home standby generator on a composite pad with electrician connecting the fuel line

    Generac 7042 & 7172 Explained: /817 and /997 Shells | PES

    Sep 22, 2026
    Modular home battery stack with inverter head and subpanel in a utility room

    Bluetti Buying Guide: AC180P vs AC200PL vs EP900 | PES

    Sep 22, 2026
    All-black residential solar panels on a shingle rooftop at low afternoon sun

    Canadian Solar 445W vs 435W: TOPHiKu6 Model Guide | PES

    Sep 22, 2026
    Portable power station with expansion battery and folding solar panel in a residential garage

    Anker SOLIX Buying Guide: C2000 Gen 2 vs F3800 vs E10 | PES

    Sep 22, 2026
    Electric unit heater mounted high on the wall of a residential garage workshop with metal conduit

    Solar Garage Heater Sizing Calculator | PES

    Sep 20, 2026
    Electrician testing a 240V receptacle with a digital multimeter in a workshop with panel behind

    kWh to Amps Calculator: 120V, 240V & 3-Phase | PES

    Sep 20, 2026
    Home battery storage unit wall-mounted in a garage charging from rooftop solar with hybrid inverter

    Solar Battery Charge Time Calculator | PES

    Sep 20, 2026
    Residential standby generator on a concrete pad beside a house at dusk with interior lights on

    What Can a Generator Run? kW Load Calculator | PES

    Sep 20, 2026
    White residential propane tank beside a standby generator on a concrete pad in a suburban backyard

    Propane Tank Sizing for Generators: Calculator | PES

    Sep 19, 2026
    Residential electric meter on an exterior wall beside the service entrance conduit of a suburban home

    Power Consumption Calculator: kWh & Cost | PES

    Sep 19, 2026
    Galvanized round HVAC ducts and flex duct branching across a residential attic with foil insulation

    Duct Size Calculator: CFM Chart by Room & Ton | PES

    Sep 19, 2026
    Electrician measuring current with a clamp meter on a copper conductor inside a residential breaker panel

    Amps to Watts Calculator: 120V, 240V & 12V | PES

    Sep 19, 2026
    Rooftop solar array with conduit down to an open main service panel showing the backfed PV breaker

    Solar 120% Rule Calculator: Max PV Breaker | PES

    Sep 19, 2026
    Commercial standby generator on a concrete pad with a wall-mounted automatic transfer switch

    kVA to kW Calculator: Power Factor Converter | PES

    Sep 19, 2026
    Open residential breaker panel with 240V double-pole breakers and copper feeders of different gauges

    240V Wire Size Calculator: Breaker & Gauge Chart | PES

    Sep 19, 2026
    Electrician pulling THHN copper conductors into EMT conduit on a hot commercial rooftop

    Ampacity Derating Calculator: NEC 310.16 & Heat | PES

    Sep 19, 2026
    Solar charge controller mounted on utility-room wall with battery bank cables

    Solar Charge Controller Sizing Calculator | PES

    Sep 19, 2026
    Residential rooftop solar array with series-string wiring and aluminum racking

    Solar String Sizing: Max Panels in Series | PES

    Sep 19, 2026
    Rooftop air-conditioning condenser unit with electrical disconnect and conduit whip

    MCA vs MOCP: AC Circuit Sizing Calculator | PES

    Sep 19, 2026
    Open residential breaker panel with labeled double-pole breakers and copper feeders

    Breaker Size Calculator: 125% Rule & Wire Chart | PES

    Sep 19, 2026
    Off-grid hybrid inverter with battery rack and conduit runs in a utility room

    Off-Grid Inverter Sizing: Continuous, Surge & Battery | PES

    Sep 18, 2026
    Electrician's hand holding a circuit breaker in front of an open load center

    Breaker Compatibility Chart: QO vs BR vs QP Panels | PES

    Sep 18, 2026
    Row of residential rooftop solar panels in soft daylight, close-up on glass cells

    Solar Panel Wattage Chart: 400W vs 450W vs 500W+ | PES

    Sep 18, 2026
    Automatic transfer switch with thick copper conductors next to breaker panel

    Transfer Switch Wire Sizing: Ampacity Chart by kW | PES

    Sep 18, 2026
    Torque screwdriver tightening a terminal lug on a copper conductor in a panel

    Lug Torque Chart: NEC 110.14 Terminal Tightness by Size &...

    Sep 18, 2026
    Electrical subpanel with feeder cable and neatly dressed branch circuits

    Subpanel Sizing Guide: Feeder Size, Spaces & Load Calc | PES

    Sep 18, 2026
    Residential rooftop solar installation at golden hour with installer tools nearby

    Solar ROI Calculator: Payback, ITC & 25-Year Savings by S...

    Sep 18, 2026
    Standby generator on concrete pad with automatic transfer switch on house wall

    Transfer Switch Sizing Guide: Amps, Circuits & ATS vs Man...

    Sep 18, 2026
    Standby generator beside a residential propane tank and natural gas line

    Standby Generator Fuel Consumption Chart: NG, Propane & D...

    Sep 17, 2026
    Home battery storage wall unit in a garage powering household circuits

    Solar Battery Backup Runtime Calculator: Hours by Load & ...

    Sep 17, 2026
    Green-insulated copper grounding conductors bonded to a ground bar in a panel

    Ground Wire Size Chart: NEC 250.122 EGC Sizing by Breaker...

    Sep 17, 2026
    Thick red and black battery cables with crimped lugs on a battery bank rack

    Battery Cable Size Chart: 12V/24V/48V Inverter & Bank Cab...

    Sep 17, 2026
    Level 2 EV charger wall-mounted in a residential garage with dedicated circuit

    EV Charger Circuit Sizing: NEC 625 Breaker, Wire & Load C...

    Sep 17, 2026

    Get Price Drops & Product Releases

    Weekly digest for installers and project managers — price drops, new stock, NEC code updates.

    Portlandia Electric Supply