Service Entrance Cable Size Calculator: 100A/200A/400A Services | PES

PES Supply, a PES Global Group Company
Β· 9 min read PES Engineering Desk β€” reviewed by a licensed master electrician
Bar chart: service entrance conductor sizes per NEC 310.12, copper vs aluminum for 100A, 200A and 400A dwelling services

Table of Contents

    Service Entrance Cable Size Calculator: 100A, 200A & 400A Services

    Reading time: ~10 min read

    πŸ“‹ Key Takeaways

    • For a dwelling service or feeder carrying the entire load, NEC 310.12 lets you size conductors at 83% of the service rating β€” a 200A dwelling service needs wire rated for just 166A: 2/0 Cu or 4/0 Al.
    • Non-dwelling and non-full-load circuits size straight off Table 310.16 (75Β°C column for these sizes): a 200A commercial service is 3/0 Cu or 250 kcmil Al β€” a full size heavier.
    • The 200A residential standard answer: 2/0-2/0-2/0-4 AWG Al SER is out of code for 310.12 dwellings (4/0 is the minimum neutral/EGC math aside) β€” use 4/0-4/0-4/0-2/0 Al SER or 2/0 Cu THHN in conduit.
    • SER is the default for interior runs to the panel; USE-2/RHW for underground laterals; THHN/XHHW-2 in conduit when the AHJ or job spec requires raceway.
    • Long service runs (200+ ft to a detached structure or ranch panel) need a voltage-drop check β€” 3% on the service can push you one or two sizes past the ampacity answer.

    "What size wire for a 200-amp service?" is the single most-asked wire question in the trade, and it has two correct answers depending on which NEC table applies. For dwelling units, NEC 310.12 (the old 310.15(B)(7)) recognizes that residential services never actually carry their full rating and lets you size at 83% β€” that's why 2/0 copper and 4/0 aluminum are everywhere. Everything else sizes off Table 310.16 at the 75Β°C column. The calculator below handles both paths: pick the service rating, material, and method, and it returns the conductor size, then runs a voltage-drop check if you give it a one-way run length.

    Building a service package? Our electrical supplies collection stocks SER, USE-2, THHN/XHHW-2, meter bases, and panels from 169 authorized brands β€” and our generators collection pairs naturally with transfer equipment for backup-ready services.

    Service Entrance Cable Calculator

    310.12 applies only when the service/feeder carries the entire dwelling load.

    Voltage-drop check at full service rating, 240V single-phase.

    Required conductor: β€”

    Typical cable assembly: β€”

    Voltage drop check: β€”

    Dwelling sizes per NEC Table 310.12 (2020/2023); standard sizes per Table 310.16 at 75Β°C (terminals at these ratings are 75Β°C listed per 110.14(C)). Voltage drop computed as 2Β·KΒ·IΒ·L/cmil with K=12.9 (Cu) / 21.2 (Al) at 240V single-phase against a 3% target β€” informational only; the NEC treats service VD as a design recommendation, not a hard limit. Final sizing belongs to the NEC 220 load calculation and the AHJ.

    Service Entrance Size Chart (Dwelling vs. Standard)

    The two code paths side by side. The dwelling column assumes NEC 310.12 applies β€” service or feeder carries the entire load of a dwelling unit. Anything else (commercial, detached-building feeders that don't carry the whole dwelling, services feeding multiple units) uses the standard column:

    Service rating Dwelling 310.12 β€” Cu Dwelling 310.12 β€” Al Standard 310.16 (75Β°C) β€” Cu Standard 310.16 β€” Al
    100 A 4 AWG 2 AWG 3 AWG 1 AWG
    125 A 2 AWG 1/0 AWG 1/0 AWG 2/0 AWG
    150 A 1 AWG 2/0 AWG 1/0 AWG 3/0 AWG
    200 A 2/0 AWG 4/0 AWG 3/0 AWG 250 kcmil
    225 A 3/0 AWG 250 kcmil 4/0 AWG 300 kcmil
    320 A (400A class) 350 kcmil 500 kcmil 400 kcmil 600 kcmil
    400 A 400 kcmil 600 kcmil 600 kcmil 800 kcmil (or parallel 250 kcmil Al)

    The 400A row deserves a footnote: most residential "400A" services are actually 320A continuous-class meter bases feeding two 200A panels, which is why 350 kcmil Cu / 500 kcmil Al is the honest dwelling answer. True 400A services at the 75Β°C column land at 600 kcmil Cu or parallel runs β€” at which point most shops run parallel 250 kcmil Al or a CT cabinet with utility-approved conductors.

    The 83% Rule (NEC 310.12), Explained Without Folklore

    310.12 isn't a discount and it isn't optional voodoo β€” it's the NEC formalizing diversity. Dwelling loads are wildly non-coincident: the range, dryer, AC, and water heater never peak together. So for a service or feeder carrying the entire load of a dwelling unit (one-family, two-family, or an individual unit of a multifamily), the conductors only need an ampacity of 83% of the service rating. 200 Γ— 0.83 = 166A, and 2/0 Cu at 75Β°C (175A) or 4/0 Al (180A) covers it.

    Where contractors get burned is applying 310.12 to things it doesn't cover:

    • Subpanel feeders that carry only part of the dwelling load β€” a 100A feeder to a garage subpanel fed from the main panel is not the entire dwelling load; it's straight 310.16 (though 2023 NEC added 310.12(B) covering feeders serving the entire load of a dwelling unit, e.g., a downstream main panel after a service disconnect).
    • Commercial and mixed-use services β€” no 83%, ever. 310.16 at the termination column.
    • Services with no capacity margin β€” the conductor must still carry the calculated NEC 220 load; if the load calc exceeds 83% of rating, the calc governs.

    SER vs. SEU vs. THHN vs. USE-2: Picking the Assembly

    Once the size is settled, the assembly question is mostly about the route:

    • SER (service entrance, round): the residential default overhead/interior answer β€” two or three insulated conductors plus a bare neutral/ground in an overall jacket, sunlight-resistant, run exposed or in raceway. 4/0-4/0-4/0-2/0 Al SER is the classic 200A dwelling assembly.
    • SEU (U-style): flat twin-hot with concentric neutral β€” older stock, still listed, less common on new work.
    • THHN/XHHW-2 in conduit: required when the AHJ wants raceway end-to-end, in commercial work, and whenever you want the neutral insulated and full-size. Costs more in labor, wins on flexibility and repairability.
    • USE-2/RHW direct burial: the underground lateral answer β€” single conductors, no overall assembly, sunlight-resistant and rated for direct earth burial. Triplex/quadplex URD assemblies are the utility-side cousin.

    One trap: NM-B and UF are not service-entrance wiring methods (338.10/340.10 restrictions aside, 338.12 limits SE use), and SER used indoors must still respect the 60Β°C NM-style rules only when the AHJ treats it as a cable assembly β€” most read SER at 75Β°C because the conductors inside are XHHW-2. Ask before you pull.

    Voltage Drop on Long Service Runs

    Rural lots, detached shops, and deep-set panels turn an ampacity answer into a voltage-drop problem fast. The math at 240V single-phase: VD = 2Β·KΒ·IΒ·L Γ· cmil, with K=12.9 for copper and 21.2 for aluminum. A 200A service run 300 feet on 4/0 Al drops about 15.4V β€” 6.4%, double the 3% design target β€” and the fix is 300 kcmil Al or stepping to copper. The NEC's 3% figures are informational notes for services (design practice, not a hard limit), but 210.19/215.2 make 3% branch/feeder numbers enforceable-adjacent in many jurisdictions, and every inspector has seen a dimming-light callback from a skinny lateral. Run the calculator above with your actual length before ordering wire; the cost of one size up is trivial next to a re-pull.

    Frequently Asked Questions

    What size wire do I need for a 200-amp service?

    For a dwelling under NEC 310.12 (the 83% rule): 2/0 AWG copper or 4/0 AWG aluminum β€” typically installed as 4/0-4/0-4/0-2/0 Al SER or 2/0 Cu THHN in conduit. For non-dwelling services sized from Table 310.16 at 75Β°C: 3/0 AWG copper or 250 kcmil aluminum. Long runs over ~200 ft should also be checked for voltage drop, which can push the size up regardless of the table answer.

    What size wire for a 100-amp service?

    Dwelling sizing per NEC 310.12: 4 AWG copper or 2 AWG aluminum β€” the common assembly is 2-2-2-4 Al SER. Standard Table 310.16 sizing at 75Β°C for non-dwelling applications: 3 AWG copper or 1 AWG aluminum. Note that some AHJs and older stock conventions still quote 2 AWG Cu for 100A β€” that's the 310.12 answer and applies only to full dwelling loads.

    What is the 83% rule for service entrance cable?

    NEC 310.12 allows conductors for a service or feeder carrying the entire load of a dwelling unit to be sized at 83% of the service rating, recognizing residential load diversity. A 200A dwelling service therefore needs conductors rated for 166A (2/0 Cu or 4/0 Al), not 200A. It does not apply to commercial services, partial-load subpanel feeders, or any case where the calculated load exceeds 83% of the rating.

    Can I use aluminum wire for a service entrance?

    Yes β€” aluminum (AA-8000 series) is the standard residential service-entrance material and what most SER and URD cable is made of. Use 75Β°C-rated terminations, wire-brush and apply antioxidant compound per manufacturer instructions, torque lugs to spec with a calibrated tool, and never use aluminum smaller than the minimums in 230.31/338.10. The two-sizes-larger penalty versus copper is already reflected in Tables 310.12 and 310.16.

    What size wire for a 400-amp residential service?

    Most residential "400A" services are 320A-class meter bases feeding two 200A panels. Under NEC 310.12 for the full dwelling load, the 320/400A row calls for 350 kcmil copper or 500 kcmil aluminum; true 400A sizing from Table 310.16 at 75Β°C is 600 kcmil copper or parallel aluminum. Because single conductors that large are unwieldy, many installs use parallel 250 kcmil Al runs or a CT cabinet β€” coordinate with the utility and AHJ before ordering.

    Quoting a Service Change or New Service?

    PES Supply stocks SER, USE-2, THHN/XHHW-2, meter bases, and panels from 169 authorized brands. Send the one-line and run lengths β€” we'll quote the complete service package at contractor pricing.

    Shop Electrical Supplies Contact Us for Bulk Pricing

    Related Resources

    Need Help Sizing This?

    Our team can help you calculate loads, select the right equipment, and source everything from one PO.

    πŸ“ž (502) 790-0600

    Email Our Team
    Solar Panels Generators Batteries / ESS EV Chargers Circuit Breakers Charge Controllers

    One PO. One Invoice. Every Trade Covered.

    PES Supply is the distribution arm of PES Global Group β€” 50,000+ SKUs from 169 authorized brands, LTL freight shipping from Louisville, KY.

    Get a Quote
    Share: X f in @

    Related Articles

    Range chart: typical lug and terminal torque in in-lb by conductor size per NEC 110.14, manufacturer label governs

    Lug Torque Chart: NEC 110.14 Terminal Tightness by Size &...

    Sep 18, 2026
    Bar chart: minimum copper feeder wire AWG per NEC 310.16 at 75C for subpanel breakers from 30A to 200A

    Subpanel Sizing Guide: Feeder Size, Spaces & Load Calc | PES

    Sep 18, 2026
    Bar chart: solar payback period in years by monthly electric bill from 100 to 300 dollars after the 30 percent federal ITC

    Solar ROI Calculator: Payback, ITC & 25-Year Savings by S...

    Sep 18, 2026
    Bar chart: generator output in amps at 240V by kW size with the next standard transfer switch rating, 8 to 26 kW

    Transfer Switch Sizing Guide: Amps, Circuits & ATS vs Man...

    Sep 18, 2026
    Bar charts: 20 kW standby generator fuel consumption at 50, 75 and 100 percent load for natural gas, propane and diesel

    Standby Generator Fuel Consumption Chart: NG, Propane & D...

    Sep 17, 2026
    Bar chart: solar battery backup runtime in hours by bank size 5-20 kWh at 500W, 1000W and 2000W loads

    Solar Battery Backup Runtime Calculator: Hours by Load & ...

    Sep 17, 2026
    Bar chart: copper equipment grounding conductor size per NEC Table 250.122 by breaker rating from 15A to 400A

    Ground Wire Size Chart: NEC 250.122 EGC Sizing by Breaker...

    Sep 17, 2026
    Bar chart: maximum DC amps per battery cable AWG at 2% voltage drop over a 10 ft run for 12V, 24V and 48V systems

    Battery Cable Size Chart: 12V/24V/48V Inverter & Bank Cab...

    Sep 17, 2026
    Bar chart: EV charger output amps 16-80A vs required breaker size at 125% continuous load per NEC 625

    EV Charger Circuit Sizing: NEC 625 Breaker, Wire & Load C...

    Sep 17, 2026
    Bar chart: maximum one-way solar wire run at 2% voltage drop by AWG for 12A, 20A and 30A strings on a 48V bus

    Solar Wire Size Calculator: PV Wire, Ampacity & Voltage D...

    Sep 17, 2026
    Bar chart: maximum 12 AWG THHN conductors per wire duct size at 20% fill per NEC 376.22(A)

    Wire Duct & Cable Tray Sizing Guide: Wireway Fill, Types ...

    Sep 17, 2026
    NEC 220.82 optional method general-load demand curve: first 10 kVA at 100%, remainder at 40%

    Electrical Load Calculation: NEC 220 Demand Factors for S...

    Sep 16, 2026
    Transformer full-load amps by kVA at 480V primary and 208V secondary, three-phase

    Transformer Sizing Calculator: kVA, Load & Voltage Select...

    Sep 16, 2026
    Box fill volume allowance per conductor in cubic inches per NEC 314.16

    Box Fill Calculator: NEC 314.16 Conductor & Device Allowa...

    Sep 16, 2026
    Max conductors per EMT conduit chart per NEC Annex C for 12 and 10 AWG THHN

    Conduit Fill Calculator: NEC Chapter 9 Tables for EMT, PV...

    Sep 16, 2026
    Running vs starting watts of common home loads for generator sizing

    Generator Sizing Calculator: Running Watts, Starting Watt...

    Sep 16, 2026
    Solar array kW needed by monthly kWh usage at 4, 5, and 6 peak sun hours

    Solar System Sizing Calculator: From kWh Usage to Array S...

    Sep 16, 2026
    Motor full-load amps at 230V single-phase vs three-phase per NEC 430.248 and 430.250

    Motor FLA Chart: NEC 430.250 Full-Load Amps, Breaker & Wi...

    Sep 16, 2026
    GEC sizing chart per NEC Table 250.66: service entrance size to copper GEC

    Grounding & Earthing Guide: NEC 250, GEC Sizing Chart & G...

    Sep 16, 2026
    Copper resistance in ohms per 1000 ft by AWG, log-scale curve 40 AWG to 4/0

    AWG Wire Gauge Chart: Diameter, Resistance, Ampacity & Ap...

    Sep 16, 2026
    Required battery bank kWh for LFP vs AGM at 2 days autonomy by daily energy use

    Battery Bank Sizing Calculator: kWh, Days of Autonomy & D...

    Sep 16, 2026
    Copper ampacity by AWG bar chart, NEC 310.16 75C column, with typical breaker pairings

    Wire Size by Amps: Ampacity Chart & Breaker Matching Guid...

    Sep 16, 2026
    Voltage drop vs distance chart for 12/10/8/6 AWG copper at 20A 120V with NEC 3% limit line

    Voltage Drop Calculator: Wire Size, Distance & NEC 3% Rul...

    Sep 16, 2026
    High-efficiency monocrystalline solar panels on a residential rooftop at golden hour

    Most Efficient Solar Panels of 2026: A Buyer's Guide for ...

    Aug 23, 2026
    Enphase Brand Guide: IQ7/IQ8 Microinverters, IQ Battery, and Installer Ecosystem

    Enphase Brand Guide: IQ7/IQ8 Microinverters, IQ Battery, ...

    Aug 12, 2026
    Wallbox home EV wall charger β€” PES Supply brand guide

    Wallbox Chargers: Brand Guide for Smart EV Charging

    Jul 06, 2026
    Victron Energy marine-blue charge controller and inverter-charger β€” PES Supply brand guide

    Victron Energy Brand Guide: SmartSolar, BlueSolar, MultiP...

    Jul 01, 2026
    Unirac flat-roof ballasted racking system β€” PES Supply brand guide

    Unirac Brand Guide: SolarMount, Flashloc, and UL 3741-Com...

    Jun 30, 2026
    Trojan Battery deep-cycle flooded batteries on rack β€” PES Supply brand guide

    Trojan Battery Brand Guide: Deep-Cycle FLA, AGM, Gel & LFP

    Jun 29, 2026
    Trina Solar commercial rooftop solar panel array β€” PES Supply brand guide

    Trina Solar Brand Guide: Vertex Series, 210mm Cells & Dea...

    Jun 24, 2026
    Sungrow residential string inverter on exterior wall β€” PES Supply brand guide

    Sungrow: Residential, Commercial, and Hybrid Inverter Bra...

    Jun 23, 2026
    sonnen wall-mounted home battery system β€” PES Supply brand guide

    Sonnen Brand Guide: All-in-One LFP Battery Systems

    Jun 22, 2026
    SolarEdge power optimizers behind rooftop panels β€” PES Supply brand guide

    SolarEdge Technologies: Power Optimizer and Inverter Bran...

    Jun 17, 2026
    Sol-Ark hybrid inverter with battery stack β€” PES Supply brand guide

    Sol-Ark: Hybrid and Off-Grid Inverter Brand Guide

    Jun 16, 2026
    SnapNrack aluminum racking rails on shingle roof β€” PES Supply brand guide

    SnapNrack Brand Guide: Ultra Rail, TopSpeed Railless, and...

    Jun 15, 2026
    SMA residential string inverter in utility room β€” PES Supply brand guide

    SMA Solar Technology: Sunny Boy, Tripower, and Commercial...

    Jun 10, 2026
    SimpliPhi Power LFP battery modules in server rack β€” PES Supply brand guide

    SimpliPhi Power Brand Guide: Ruggedized LFP Batteries

    Jun 09, 2026
    Silfab Solar black-frame solar panels on residential roof β€” PES Supply brand guide

    Silfab Solar Brand Guide: Premium Mono PERC, AX Series & ...

    Jun 08, 2026
    Schneider Electric Conext XW Pro style off-grid inverter and MPPT controller β€” PES Supply brand guide

    Schneider Electric: Conext XW Pro, MPPT Controllers, and ...

    Jun 03, 2026
    REC rooftop solar panel array β€” PES Supply brand guide

    REC Group Brand Guide: Alpha Series, HJT Technology & Dea...

    Jun 02, 2026
    Quick Mount PV roof flashing and mounting foot on shingles β€” PES Supply brand guide

    Quick Mount PV Brand Guide: QBase, Flashing Systems, and ...

    Jun 01, 2026
    Pylontech server-rack LiFePO4 batteries β€” PES Supply brand guide

    Pylontech Brand Guide: Modular LFP Batteries (US Series &...

    May 27, 2026
    OutBack Power off-grid inverter-charger power panel β€” PES Supply brand guide

    OutBack Power Brand Guide: FLEXmax Controllers, FlexPower...

    May 26, 2026
    Morningstar solar charge controller above battery bank β€” PES Supply brand guide

    Morningstar Corporation Brand Guide: TriStar, ProStar, an...

    May 25, 2026
    Mission Solar solar panels in a US manufacturing facility β€” PES Supply brand guide

    Mission Solar Energy Brand Guide: Made-in-USA Modules, BA...

    May 20, 2026
    MidNite Solar MPPT charge controller and steel enclosure β€” PES Supply brand guide

    MidNite Solar Brand Guide: Classic MPPT Controllers, E-Pa...

    May 19, 2026
    LONGi Solar monocrystalline solar panel detail β€” PES Supply brand guide

    LONGi Solar Brand Guide: Hi-MO Series, BC Cell Technology...

    May 18, 2026
    Kohler (Rehlko) premium residential standby generator β€” PES Supply brand guide

    Kohler Energy (Rehlko): Brand Guide for Premium Standby P...

    May 13, 2026
    Jinko Solar residential rooftop solar panels β€” PES Supply brand guide

    Jinko Solar Brand Guide: Tiger Neo TOPCon Modules & Deale...

    May 12, 2026

    Get Price Drops & Product Releases

    Weekly digest for installers and project managers β€” price drops, new stock, NEC code updates.

    PES Supply, a PES Global Group Company