Wire Size by Amps: Ampacity Chart & Breaker Matching Guide (NEC 310.16) | PES

PES Supply, a PES Global Group Company
· 10 min read PES Engineering Desk — reviewed by a licensed master electrician
Assorted THHN copper wire gauges in colored insulation laid out on a workbench

Table of Contents

    Updated September 2026 — refreshed against the live PES catalog; product pricing verified 2026-09-26.

    Wire Size by Amps: Ampacity Chart & Breaker Matching Guide (NEC 310.16)

    Reading time: ~10 min read

    📋 Key Takeaways

    • Match the breaker to the wire, never the other way around: 15 A → 14 AWG, 20 A → 12 AWG, 30 A → 10 AWG, per NEC 240.4(D).
    • Most residential and commercial terminations are rated 75 °C, so the 75 °C column of NEC Table 310.16 governs even when you pull 90 °C THHN.
    • Continuous loads (3 hours or more) must be sized at 125% of the load current per NEC 210.20(A) — that rule alone forces one size up on many circuits.
    • The 90 °C column is only usable for derating calculations (ambient temperature and conduit fill), not for final ampacity on 75 °C-rated equipment.
    • Ampacity is only half the check — verify voltage drop on any run longer than about 100 feet.

    Every wire in a building answers to two numbers: the load it carries and the breaker that protects it. Get the pairing wrong in one direction and the insulation cooks before the breaker trips; get it wrong in the other and you're paying for copper you didn't need. This guide gives you the NEC Table 310.16 ampacity values you'll actually use — copper THHN at 75 °C and 90 °C, plus aluminum — a breaker-to-wire matching table, the 125% continuous-load rule, and a quick lookup tool. Pull the wire and breakers from our electrical supplies collection when you're ready to order.

    Breaker-to-Wire Quick Lookup

    Breaker already sized for a continuous load? NEC 210.20(A) requires the breaker at 125% of the load, so a 20 A breaker carries at most 16 A continuous.

    Minimum wire size: —

    Based on the NEC Table 310.16 75 °C column, the NEC 240.4(D) small-conductor limits, and the 240.4(B) round-up rule. Ambient-temperature and conduit-fill derating may force a larger size — see below.

    NEC Table 310.16 Ampacity Chart (14 AWG – 4/0)

    Table 310.16 lists allowable ampacities for insulated conductors rated up to 2,000 V, at 30 °C ambient, with no more than three current-carrying conductors in a raceway. These are the values for the sizes you'll pull every day:

    Wire Size Copper 75 °C (THHN/THWN) Copper 90 °C (THHN-2) Aluminum 75 °C Aluminum 90 °C
    14 AWG 20 A 25 A — —
    12 AWG 25 A 30 A 20 A 25 A
    10 AWG 35 A 40 A 30 A 35 A
    8 AWG 50 A 55 A 40 A 45 A
    6 AWG 65 A 75 A 50 A 55 A
    4 AWG 85 A 95 A 65 A 75 A
    3 AWG 100 A 115 A 75 A 85 A
    2 AWG 115 A 130 A 90 A 100 A
    1 AWG 130 A 145 A 100 A 115 A
    1/0 AWG 150 A 170 A 120 A 135 A
    2/0 AWG 175 A 195 A 135 A 150 A
    3/0 AWG 200 A 225 A 155 A 175 A
    4/0 AWG 230 A 260 A 180 A 205 A

    Values from NEC Table 310.16. Assumes 30 °C (86 °F) ambient and three or fewer current-carrying conductors per raceway.

    Why the 75 °C Column Usually Wins

    THHN wire is 90 °C-rated, so it's tempting to size from the 90 °C column. Don't. NEC 110.14(C) requires you to use the ampacity column that matches the weakest termination in the circuit, and nearly every breaker, panel, and disconnect rated 100 A or less is listed for 75 °C (or 60 °C on older gear). The 90 °C column still earns its keep in one place: as the starting point for derating. If you're correcting for a hot attic (Table 310.15(B)(1)) or a conduit packed with current-carrying conductors (Table 310.15(C)(1)), you may start the math from the conductor's actual 90 °C rating — but the final derated number still can't exceed the 75 °C column value at the terminations.

    Breaker-to-Wire Matching Table

    The breaker protects the wire, so the wire's ampacity must be at least the breaker's rating — with the NEC 240.4(D) small-conductor caps applied to 14, 12, and 10 AWG, and the 240.4(B) round-up rule allowing the next standard breaker size above ampacity for larger conductors:

    Breaker Min. Copper (75 °C) Min. Aluminum (75 °C) Typical Use
    15 A 14 AWG — Lighting, general receptacles
    20 A 12 AWG — Kitchen/bath receptacles, small appliances
    30 A 10 AWG 8 AWG* Dryers, small AC units, water heaters
    40 A 8 AWG 6 AWG Ranges, EV chargers (40 A)
    50 A 8 AWG 6 AWG Ranges, welders, hot tubs
    60 A 6 AWG 4 AWG Subpanels, large AC condensers
    70 A 4 AWG 3 AWG Subpanels (round-up from 65 A ampacity)
    80 A 4 AWG 2 AWG Subpanels, EV chargers (80 A circuit)
    100 A 3 AWG 1 AWG Small services, large subpanels
    125 A 1/0 AWG 2/0 AWG Services and main-lug panels
    150 A 2/0 AWG 4/0 AWG Residential services
    200 A 3/0 AWG 250 kcmil Standard residential service

    *Aluminum is uncommon below 8 AWG in modern work; 240.4(D) caps 12 AWG aluminum at 15 A and 10 AWG aluminum at 25 A on branch circuits. For 100 A+ feeders, also check the dwelling-unit service sizing allowance in NEC 310.12, which permits smaller conductors for residential services.

    The 125% Continuous Load Rule (NEC 210.20)

    A continuous load — anything expected to run at maximum current for three hours or more — gets special treatment. NEC 210.20(A) requires the overcurrent device to be rated at least 125% of the continuous load, and 210.19(A)(1) applies the same multiplier to the conductor:

    Breaker & wire ampacity ≥ 1.25 × continuous load + 100% of non-continuous load

    What counts as continuous in the real world: EV chargers, commercial lighting, water heaters, heat pumps, server rooms, and any load an occupancy sensor keeps on all day. A 40 A EV charger is the classic case: 40 A × 1.25 = 50 A, so you need a 50 A breaker and 8 AWG copper minimum — not the 40 A breaker and 8 AWG you'd grab off the nameplate alone. Solar inverter output circuits get the same treatment (NEC 690.8/690.9 apply their own 125% factors), which is why a 7.7 kW inverter at 32 A lands on a 40 A breaker with 8 AWG, not 10 AWG.

    Exception worth knowing: if both the breaker and its enclosure are listed for 100% continuous operation, you can skip the 125% multiplier. That's common on large frame breakers, rare on residential load centers.

    When You Must Upsize Beyond the Chart

    • Continuous loads: the 125% rule above — the single most common reason a "code-minimum" install fails inspection.
    • Ambient temperature: ampacities assume 30 °C. Attics, rooftops, and boiler rooms run hotter; apply the Table 310.15(B)(1) correction factors. Rooftop solar conduit can add another 20–30 °C of effective ambient.
    • Conduit fill: more than three current-carrying conductors in one raceway triggers the Table 310.15(C)(1) adjustment — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20.
    • Voltage drop: ampacity keeps the wire from overheating; it says nothing about delivered voltage. On runs past ~100 ft, verify drop against the NEC 3% recommendation and upsize as needed.
    • Motor and HVAC circuits: NEC 240.4(G) routes these to Article 430/440 rules, where the breaker can be sized well above conductor ampacity to survive inrush — a deliberate, code-sanctioned exception to the matching table above.

    Common Mistakes That Get Installers Red-Tagged

    • Sizing from the 90 °C column because the spool says THHN — the terminations say 75 °C, and 110.14(C) sides with the terminations.
    • Ignoring 240.4(D): 12 AWG copper carries 25 A at 75 °C, but you may not protect it with a 25 A breaker — the cap is 20 A.
    • Forgetting the neutral counts as current-carrying on nonlinear loads (offices full of LED drivers and switch-mode supplies), which changes your conduit-fill derating math.
    • Pairing aluminum wire with CU-only lugs: aluminum conductors need AL-rated terminations and anti-oxidant compound per 110.14.
    • Upsizing the breaker to stop nuisance trips instead of fixing the load or the wiring. The breaker is the safety valve for the wire; bigger is not safer.

    Frequently Asked Questions

    What size wire do I need for a 20 amp circuit?

    12 AWG copper minimum, per NEC 240.4(D). Although 12 AWG THHN is rated 25 A at 75 °C, the small-conductor rule caps its overcurrent protection at 20 A. For a continuous 20 A load, apply the 125% rule: you need a 25 A-rated conductor path, so size the wire for 25 A and use a 25 A or 20 A breaker as the load allows — most installers simply step to 10 AWG on long or hot runs.

    Can I use the 90 °C column of Table 310.16?

    Only as a starting point for temperature and conduit-fill derating. NEC 110.14(C) limits the final ampacity to the column matching your termination rating — 75 °C for virtually all equipment rated 100 A or less and most larger modern gear. The final, derated number may never exceed the termination column value.

    What wire size is required for a 100 amp service?

    From the 75 °C column: 3 AWG copper or 1 AWG aluminum. However, NEC 310.12 allows smaller conductors for dwelling-unit services — 4 AWG copper or 2 AWG aluminum for a 100 A residential service — because diversified residential loads rarely approach the service rating. Check your local amendments; some jurisdictions don't adopt 310.12.

    Does aluminum wire need to be bigger than copper?

    Yes — aluminum has about 61% of copper's conductivity, so you typically go up two sizes: a run needing 6 AWG copper takes 4 AWG aluminum. Aluminum is standard practice for service entrance and large feeders because the installed cost is far lower, but it requires AL-rated lugs, anti-oxidant compound, and correct torque.

    What happens if the wire is bigger than the breaker requires?

    Nothing bad — oversizing wire is always electrically safe (the breaker still protects it). You trade money for lower voltage drop, less heat, and headroom for future load growth. The only hard limits are physical: the conductor must fit the terminal, or you splice down to a listed pigtail size.

    Wire, Breakers, and Panels — One PO

    PES Supply stocks THHN, feeders, breakers, and load centers from 169 authorized brands. Send your panel schedule and we'll quote the whole bill of material with trade pricing.

    Shop Electrical Supplies Contact Us for a Quote

    Related Resources

    Need pricing or availability on anything in this guide?

    Portlandia Electric Supply dropships direct from the manufacturer — most items Ship Direct with lead times stated up front, no surprises.

    Get a quote from PESBulk, pallet and contractor pricing available.

    Related PES Supply guides

    Need Help Sizing This?

    Our team can help you calculate loads, select the right equipment, and source everything from one PO.

    📞 (502) 790-0600

    Email Our Team
    Solar Panels Generators Batteries / ESS EV Chargers Circuit Breakers Charge Controllers

    One PO. One Invoice. Every Trade Covered.

    PES Supply is the distribution arm of PES Global Group — 50,000+ SKUs from 169 authorized brands, LTL freight shipping from Louisville, KY.

    Get a Quote
    Share: X f in @

    Related Articles

    Generac 22kW vs Kohler 20kW Standby Generator: Real Specs

    Generac 22kW vs Kohler 20kW Standby Generator: Real Specs

    Oct 19, 2026
    Best Solar Panels for Cloudy Climates: What Actually Matters

    Best Solar Panels for Cloudy Climates: What Actually Matters

    Oct 02, 2026
    Pallet of boxed solar panels in shrink wrap on a warehouse floor with a liftgate box truck behind

    Solar Panel Pallet Cost, Delivered: $/W Math | PES

    Sep 23, 2026
    Commercial flat-roof solar array with copper grounding lugs bonding aluminum racking rails

    Commercial Solar Grounding BOM: NEC 690.43 | PES

    Sep 23, 2026
    All-black solar panels on a residential shingle rooftop in late afternoon sunlight

    Aptos DNA 460W Panel: Specs, Price & Family | PES

    Sep 23, 2026
    Residential standby generator on a concrete pad beside a brick home with conduit to a wall-mounted transfer switch

    Briggs PowerProtect 13kW Shell + Symphony II ATS | PES

    Sep 23, 2026
    Full wooden pallet stacked with boxed solar panels in shrink film on a warehouse floor with a flatbed liftgate truck behind

    Buying Solar Panels by the Pallet: Pro Guide | PES

    Sep 23, 2026
    Wall-mounted hybrid solar inverter in a tidy residential utility room with metal conduit, red and black battery cables and a subpanel

    Sol-Ark vs GoodWe Hybrid Inverter Guide | PES

    Sep 23, 2026
    Two modern wall-mounted home battery storage units side by side on a clean residential garage wall with conduit and a disconnect

    EG4 Battery vs Tesla Powerwall 3: Honest Comparison | PES

    Sep 23, 2026
    Caribbean-style home in Puerto Rico with a rooftop solar array and a wall-mounted home battery, palm trees and bright sun

    Puerto Rico Solar + Battery Resilience Guide | PES

    Sep 23, 2026
    All-black residential rooftop solar panels with a uniform busbar-free surface on a shingle roof

    AIKO Solar Panels: Price, Specs & ABC Technology | PES

    Sep 23, 2026
    Commercial ground-mount bifacial solar array on light gravel under a clear sky

    Bila Solar AA-530US: Domestic Content Panels & ITC | PES

    Sep 23, 2026
    Gloved hand clamping a split-core current transformer around a conductor inside an open electrical panel

    Accu-CT Split-Core Sensors Explained: 333mV CTs | PES

    Sep 23, 2026
    Floor-standing home battery storage cabinet beside a wall-mounted hybrid inverter in a residential garage

    Big Battery NEXUS 15kWh Explained: Specs & Scaling | PES

    Sep 23, 2026
    Through-the-wall PTAC air conditioner installed on a hotel guestroom wall beneath a large window

    Amana PTAC Sizing Guide: 7,000–15,000 BTU Ladder | PES

    Sep 23, 2026
    Residential standby generator on a composite pad beside a suburban home with an electrician work van in the driveway

    Champion aXis Generator Guide: 8.5kW, 14kW & 22kW | PES

    Sep 23, 2026
    Air-cooled home standby generator on a composite pad with electrician connecting the fuel line

    Generac 7042 & 7172 Explained: /817 and /997 Shells | PES

    Sep 22, 2026
    Modular home battery stack with inverter head and subpanel in a utility room

    Bluetti Buying Guide: AC180P vs AC200PL vs EP900 | PES

    Sep 22, 2026
    All-black residential solar panels on a shingle rooftop at low afternoon sun

    Canadian Solar 445W vs 435W: TOPHiKu6 Model Guide | PES

    Sep 22, 2026
    Portable power station with expansion battery and folding solar panel in a residential garage

    Anker SOLIX Buying Guide: C2000 Gen 2 vs F3800 vs E10 | PES

    Sep 22, 2026
    Electric unit heater mounted high on the wall of a residential garage workshop with metal conduit

    Solar Garage Heater Sizing Calculator | PES

    Sep 20, 2026
    Electrician testing a 240V receptacle with a digital multimeter in a workshop with panel behind

    kWh to Amps Calculator: 120V, 240V & 3-Phase | PES

    Sep 20, 2026
    Home battery storage unit wall-mounted in a garage charging from rooftop solar with hybrid inverter

    Solar Battery Charge Time Calculator | PES

    Sep 20, 2026
    Residential standby generator on a concrete pad beside a house at dusk with interior lights on

    What Can a Generator Run? kW Load Calculator | PES

    Sep 20, 2026
    White residential propane tank beside a standby generator on a concrete pad in a suburban backyard

    Propane Tank Sizing for Generators: Calculator | PES

    Sep 19, 2026
    Residential electric meter on an exterior wall beside the service entrance conduit of a suburban home

    Power Consumption Calculator: kWh & Cost | PES

    Sep 19, 2026
    Galvanized round HVAC ducts and flex duct branching across a residential attic with foil insulation

    Duct Size Calculator: CFM Chart by Room & Ton | PES

    Sep 19, 2026
    Electrician measuring current with a clamp meter on a copper conductor inside a residential breaker panel

    Amps to Watts Calculator: 120V, 240V & 12V | PES

    Sep 19, 2026
    Rooftop solar array with conduit down to an open main service panel showing the backfed PV breaker

    Solar 120% Rule Calculator: Max PV Breaker | PES

    Sep 19, 2026
    Commercial standby generator on a concrete pad with a wall-mounted automatic transfer switch

    kVA to kW Calculator: Power Factor Converter | PES

    Sep 19, 2026
    Open residential breaker panel with 240V double-pole breakers and copper feeders of different gauges

    240V Wire Size Calculator: Breaker & Gauge Chart | PES

    Sep 19, 2026
    Electrician pulling THHN copper conductors into EMT conduit on a hot commercial rooftop

    Ampacity Derating Calculator: NEC 310.16 & Heat | PES

    Sep 19, 2026
    Solar charge controller mounted on utility-room wall with battery bank cables

    Solar Charge Controller Sizing Calculator | PES

    Sep 19, 2026
    Residential rooftop solar array with series-string wiring and aluminum racking

    Solar String Sizing: Max Panels in Series | PES

    Sep 19, 2026
    Rooftop air-conditioning condenser unit with electrical disconnect and conduit whip

    MCA vs MOCP: AC Circuit Sizing Calculator | PES

    Sep 19, 2026
    Open residential breaker panel with labeled double-pole breakers and copper feeders

    Breaker Size Calculator: 125% Rule & Wire Chart | PES

    Sep 19, 2026
    Off-grid hybrid inverter with battery rack and conduit runs in a utility room

    Off-Grid Inverter Sizing: Continuous, Surge & Battery | PES

    Sep 18, 2026
    Electrician's hand holding a circuit breaker in front of an open load center

    Breaker Compatibility Chart: QO vs BR vs QP Panels | PES

    Sep 18, 2026
    Row of residential rooftop solar panels in soft daylight, close-up on glass cells

    Solar Panel Wattage Chart: 400W vs 450W vs 500W+ | PES

    Sep 18, 2026
    Automatic transfer switch with thick copper conductors next to breaker panel

    Transfer Switch Wire Sizing: Ampacity Chart by kW | PES

    Sep 18, 2026
    Torque screwdriver tightening a terminal lug on a copper conductor in a panel

    Lug Torque Chart: NEC 110.14 Terminal Tightness by Size &...

    Sep 18, 2026
    Electrical subpanel with feeder cable and neatly dressed branch circuits

    Subpanel Sizing Guide: Feeder Size, Spaces & Load Calc | PES

    Sep 18, 2026
    Residential rooftop solar installation at golden hour with installer tools nearby

    Solar ROI Calculator: Payback, ITC & 25-Year Savings by S...

    Sep 18, 2026
    Standby generator on concrete pad with automatic transfer switch on house wall

    Transfer Switch Sizing Guide: Amps, Circuits & ATS vs Man...

    Sep 18, 2026
    Standby generator beside a residential propane tank and natural gas line

    Standby Generator Fuel Consumption Chart: NG, Propane & D...

    Sep 17, 2026
    Home battery storage wall unit in a garage powering household circuits

    Solar Battery Backup Runtime Calculator: Hours by Load & ...

    Sep 17, 2026
    Service entrance mast and meter base on a residential exterior wall

    Service Entrance Cable Size Calculator: 100A/200A/400A Se...

    Sep 17, 2026
    Green-insulated copper grounding conductors bonded to a ground bar in a panel

    Ground Wire Size Chart: NEC 250.122 EGC Sizing by Breaker...

    Sep 17, 2026
    Thick red and black battery cables with crimped lugs on a battery bank rack

    Battery Cable Size Chart: 12V/24V/48V Inverter & Bank Cab...

    Sep 17, 2026
    Level 2 EV charger wall-mounted in a residential garage with dedicated circuit

    EV Charger Circuit Sizing: NEC 625 Breaker, Wire & Load C...

    Sep 17, 2026

    Get Price Drops & Product Releases

    Weekly digest for installers and project managers — price drops, new stock, NEC code updates.

    Portlandia Electric Supply