AWG Wire Gauge Chart: Diameter, Resistance, Ampacity & Applications | PES

PES Supply, a PES Global Group Company
· 12 min read PES Engineering Desk — reviewed by a licensed master electrician
Close-up of stripped copper wire ends in several AWG gauges side by side

Table of Contents

    AWG Wire Gauge Chart: Diameter, Resistance, Ampacity & Applications

    The complete American Wire Gauge table — 40 AWG through 4/0 — with diameters, circular mils, copper resistance, NEC ampacity quick picks, and the voltage-drop math we use on every job ticket.

    Every week somebody calls the counter asking "what wire do I need for a 100-amp subpanel" or "is 12 gauge enough for my solar strings," and every week the answer starts with the same chart. American Wire Gauge is the sizing system behind essentially every conductor sold in North America, and once you understand that it's logarithmic — three gauge numbers down doubles the cross-section and halves the resistance — you can sanity-check any spec sheet in seconds. Below is the full reference table, the ampacity numbers that matter under NEC 310.16, and the voltage-drop formula that decides real-world wire size more often than ampacity does. When you're ready to buy, our electrical supplies collection stocks the building wire, PV wire, and battery cable this chart covers.

    Complete AWG Chart: 40 AWG to 4/0

    Diameters are for solid bare copper conductor. Circular mils (kcmil above 4/0) are the cross-sectional area unit the NEC uses — one circular mil is the area of a circle one mil (0.001 in) in diameter. Resistance values are for annealed copper at 20°C (68°F); expect roughly 2% higher at 50°C conductor temperature and about 61% higher for aluminum of the same gauge.

    AWG Diameter (in) Diameter (mm) Area (circular mils) Copper Ω / 1,000 ft @ 20°C
    40 0.003145 0.07987 10 1049
    39 0.003531 0.08969 12 831.8
    38 0.003965 0.1007 16 659.6
    37 0.004453 0.1131 20 523.1
    36 0.005000 0.1270 25 414.8
    35 0.005615 0.1426 32 329.0
    34 0.006305 0.1601 40 260.9
    33 0.007080 0.1798 50 206.9
    32 0.007950 0.2019 63 164.1
    31 0.008928 0.2268 80 130.1
    30 0.01003 0.2546 101 103.2
    29 0.01126 0.2859 127 81.83
    28 0.01264 0.3211 160 64.90
    27 0.01420 0.3606 202 51.47
    26 0.01594 0.4049 254 40.81
    25 0.01790 0.4547 320 32.37
    24 0.02010 0.5106 404 25.67
    23 0.02257 0.5733 509 20.36
    22 0.02535 0.6438 642 16.14
    21 0.02846 0.7229 810 12.80
    20 0.03196 0.8118 1,022 10.15
    19 0.03589 0.9116 1,288 8.051
    18 0.04030 1.024 1,624 6.385
    17 0.04526 1.150 2,048 5.063
    16 0.05082 1.291 2,583 4.015
    15 0.05707 1.450 3,257 3.184
    14 0.06408 1.628 4,107 2.525
    13 0.07196 1.828 5,178 2.003
    12 0.08081 2.053 6,530 1.588
    11 0.09074 2.305 8,234 1.260
    10 0.1019 2.588 10,383 0.9988
    9 0.1144 2.906 13,093 0.7921
    8 0.1285 3.264 16,510 0.6282
    7 0.1443 3.665 20,818 0.4982
    6 0.1620 4.115 26,251 0.3951
    5 0.1819 4.621 33,102 0.3133
    4 0.2043 5.189 41,741 0.2485
    3 0.2294 5.827 52,635 0.1970
    2 0.2576 6.544 66,371 0.1563
    1 0.2893 7.348 83,693 0.1239
    1/0 0.3249 8.251 105,535 0.09827
    2/0 0.3648 9.266 133,077 0.07793
    3/0 0.4096 10.40 167,806 0.06180
    4/0 0.4600 11.68 211,600 0.04901

    Two patterns worth memorizing: every 3-gauge step doubles or halves the circular mils (10 AWG ≈ 10,380 cmil; 4/0 ≈ 211,600 cmil), and every 6-gauge step doubles or halves the diameter. That's the entire system — the rest is arithmetic.

    Ampacity Quick Table (Copper, NEC 310.16)

    Ampacity is where charts meet code. The numbers below are the NEC 310.16 75°C column for copper conductors in raceway or cable — the column that governs most residential and light-commercial work, since breaker and equipment terminations are typically rated 75°C. The "typical breaker" column applies the NEC 240.4(D) small-conductor rules, which cap 14/12/10 AWG at 15/20/30A regardless of what the table permits.

    AWG Ampacity @ 60°C (TW, UF) Ampacity @ 75°C (THHN, THWN-2) Ampacity @ 90°C (derating only) Typical max breaker
    14 15A 20A 25A 15A
    12 20A 25A 30A 20A
    10 30A 35A 40A 30A
    8 40A 50A 55A 40–50A
    6 55A 65A 75A 60A
    4 70A 85A 95A 80A
    3 85A 100A 115A 100A
    2 95A 115A 130A 100–110A
    1 110A 130A 145A 125A
    1/0 125A 150A 170A 150A
    2/0 145A 175A 195A 175A
    3/0 165A 200A 225A 200A
    4/0 195A 230A 260A 225A

    Derating is not optional

    These are 30°C-ambient, three-current-carrying-conductor values. A rooftop conduit in Arizona at 60°C ambient strips 40%+ of the 75°C ampacity, and more than three current-carrying conductors in one raceway triggers NEC 310.15(C)(1) adjustment factors. Solar installers: the 90°C column is for derating math only — final ampacity is still limited by the 75°C termination rating.

    Interactive AWG Lookup Tool

    Select a gauge to pull every spec from the chart at once, or work the other direction — enter a load in amps and the tool returns the smallest copper conductor that carries it under the NEC 240.4(D) breaker rules. Ampacity answers are 75°C copper values; always re-check voltage drop on runs over ~75 ft and size continuous loads at 125%.

    Full chart range: 40 AWG (winding wire) through 4/0 (service and battery cable).

    Returns the smallest copper gauge per NEC 240.4(D). Leave blank to use gauge lookup only.

    —
    Diameter (in / mm)
    —
    Area (circular mils / mm²)
    —
    Copper Ω / 1,000 ft @ 20°C
    —
    Ampacity 60 / 75 / 90°C — typical breaker
    —
    Recommended gauge for entered amps (Cu)

    Common Application Quick Picks

    The counter-question cheat sheet, with the code basis behind each answer:

    What gauge for…

    • 20A branch circuit (receptacles, garage, kitchen small-appliance): 12 AWG copper. NEC 240.4(D) caps 12 AWG at 20A even though the table allows more.
    • 30A dryer or RV receptacle: 10 AWG copper, 30A breaker.
    • 50A range or Level 2 EV charger (40A continuous): 6 AWG copper for hardwired continuous loads — EV charging is a continuous load under NEC 625, so size at 125%.
    • 100A subpanel feeder: 3 AWG copper THHN (100A @ 75°C) or 1 AWG aluminum. For the main feeder serving an entire dwelling, NEC 310.12 lets you drop to 4 AWG copper / 2 AWG aluminum — a frequent point of inspection debates.
    • Solar array strings (10–15A per string): 10 AWG PV wire is the industry default — it carries the current with margin and holds voltage drop down on long rooftop runs. High-current strings above ~25A step to 8 AWG.
    • Battery-to-inverter cables (48V, 100–200A): 2 AWG to 2/0 fine-strand copper welding/battery cable. At DC, voltage drop is the design constraint, not ampacity — see below.
    • Generator to transfer switch: sized to the generator's output breaker per NEC 445.13 — a 22 kW standby unit at 240V (92A) typically lands on 3 AWG copper.

    Voltage Drop: The Constraint That Actually Sizes the Wire

    Ampacity keeps insulation from melting. Voltage drop keeps equipment working. The NEC doesn't mandate a limit (it's an informational note), but the industry targets are 3% maximum on any branch circuit or feeder and 5% total — and for 12/24/48V battery and solar DC systems you should hold 2% or better, because 2V lost on a 12V system is 17%, not 1.7%.

    For single-phase and DC circuits: VD = 2 × L × I × R ÷ 1,000, where L is one-way length in feet, I is load current, and R is the Ω/1,000 ft value from the chart above. The factor of 2 accounts for the round trip out and back.

    Worked example: 48V battery bank to inverter

    • Inverter draws 100A continuous; one-way cable run is 10 ft; candidate conductor 2 AWG (0.1563 Ω/1,000 ft).
    • VD = 2 × 10 × 100 × 0.1563 ÷ 1,000 = 0.31V — 0.65% of 48V. Excellent.
    • The same run at 12V (a 1,200W inverter): VD = 0.31V is now 2.6% — marginal — and the 12V inverter is pulling 400A, so you'd be on 4/0 cable and still dropping over 1V. This is why residential storage standardizes on 48V.

    Worked example: 20A circuit, 100 ft run

    • 12 AWG at 20°C: VD = 2 × 100 × 20 × 1.588 ÷ 1,000 = 6.35V — 5.3% at 120V. Fails the 3% target.
    • 10 AWG: VD = 2 × 100 × 20 × 0.9988 ÷ 1,000 = 4.0V — 3.3%. Marginal; 8 AWG gets you to 2.1%.
    • Lesson: on any run past ~75 ft at 120V, voltage drop — not ampacity — picks the wire.

    Solid vs Stranded — and the Skin-Effect Question

    Same AWG, same copper, same ampacity: solid and stranded conductors carry identical current because cross-sectional area is what matters, and both are built to the same circular-mil spec. The differences are mechanical. Solid wire (through 10 AWG in building cable) is cheaper, holds its shape in boxes, and terminates cleanly under device screws — it's what NM-B romex is made of. Stranded wire flexes without work-hardening and survives vibration, so it's mandatory for anything that moves, and it's the standard construction from 8 AWG up because a solid 2/0 conductor simply cannot be pulled around a conduit bend. Fine-strand battery and welding cable takes this further for tight routing in inverter bays. Two practical notes: stranded conductors measure slightly larger in overall diameter than solid of the same AWG (the air gaps between strands), and stranded requires the right termination — use ferrules or lugs rated for stranded wire, never a bare wrap under a screw head.

    Skin effect — current crowding toward the conductor surface at higher frequencies — is real physics that rarely matters at power-line frequency. At 60 Hz, the skin depth in copper is about 8.5 mm, deeper than the radius of a 4/0 conductor (~5.9 mm), so the entire cross-section of any wire in this chart carries current essentially uniformly. You can ignore skin effect for every AC branch circuit, feeder, and DC battery cable you'll ever pull. Where it does bite: high-frequency applications — inverter PWM output harmonics, RF transmission, induction heating, and data/signal wiring — which is why those worlds use Litz wire, braid, or plated conductors. If a salesman cites skin effect to upsell you exotic building wire for a 60 Hz panel feeder, hang up.

    Frequently Asked Questions

    What gauge wire do I need for a 20-amp circuit? 12 AWG copper, on a 20A breaker, per NEC 240.4(D). The table technically allows 25A on 12 AWG THHN at 75°C, but the small-conductor rule caps the overcurrent device at 20A. For runs over ~75 feet, bump to 10 AWG for voltage drop — same breaker.

    What size wire for a 100-amp subpanel? 3 AWG copper THHN/THWN-2 at the 75°C column, or 1 AWG aluminum with an anti-oxidant compound and AL-rated lugs. If the feeder serves the entire dwelling load, NEC 310.12 permits 4 AWG copper / 2 AWG aluminum — but confirm your AHJ applies that table before you order wire.

    What gauge wire should I use for solar panel strings? 10 AWG PV wire (USE-2 or PV-rated) is the standard for strings up to ~25A and covers most residential arrays with comfortable voltage-drop margins. Source circuits are sized at 156% of short-circuit current under NEC 690.8 — 10 AWG handles typical 13–15A Isc strings with room to spare even after rooftop temperature derating.

    Is stranded or solid wire better? Neither — same ampacity at the same gauge. Solid wins for in-wall branch wiring (cost, termination, shape retention); stranded wins for anything flexed, vibrated, or larger than 10 AWG. Match the termination hardware to the construction and both perform identically electrically.

    Does insulation type change ampacity? Yes. The conductor gauge sets the resistance, but the insulation temperature rating (60°C TW/UF, 75°C THWN-2, 90°C THHN) sets which NEC 310.16 column you use. The same 10 AWG conductor is worth 30A in UF cable and 35A in THWN-2 — before derating.

    How does aluminum compare to copper at the same gauge? Aluminum carries roughly two AWG sizes less than copper — 2 AWG aluminum ≈ 4 AWG copper in ampacity — with about 61% higher resistance per foot. It's the standard for service entrance and large feeders (SER, XHHW-2) because the cost per amp is unbeatable at those sizes; it demands AL-rated terminations, proper torque, and antioxidant paste.

    What is a circular mil? The cross-sectional area of a circle 0.001 inch (one mil) in diameter. Area in circular mils is simply the diameter in mils squared — no π involved — which is why the NEC uses it for conductor sizing math. Above 4/0, conductors are specified directly in kcmil (thousands of circular mils): 250, 350, 500 kcmil and up.

    Can I connect aluminum and copper wire together? Never directly — the galvanic pair corrodes and the joint loosens as the metals expand at different rates. Use listed dual-rated (AL/CU) connectors, AlumiConn-style lug connectors, or COPALUM crimps for pigtailing. This is a house-fire-class mistake, not a technicality.

    Sources: NEC 2023 Tables 310.16 and 310.12, NEC Chapter 9 Table 8 conductor properties, ASTM B3/B8 conductor standards, and PES Supply counter tickets. Need wire by the foot, PV wire by the spool, or battery cable cut and lugged to length? Get a free quote — contractor and bulk pricing available across our electrical supplies inventory.

    Related PES Supply guides

    También disponible en español: lea esta guía en español.

    Need Help Sizing This?

    Our team can help you calculate loads, select the right equipment, and source everything from one PO.

    📞 (502) 790-0600

    Email Our Team
    Solar Panels Generators Batteries / ESS EV Chargers Circuit Breakers Charge Controllers

    One PO. One Invoice. Every Trade Covered.

    PES Supply is the distribution arm of PES Global Group — 50,000+ SKUs from 169 authorized brands, LTL freight shipping from Louisville, KY.

    Get a Quote
    Share: X f in @

    Related Articles

    Generac 22kW vs Kohler 20kW Standby Generator: Real Specs

    Generac 22kW vs Kohler 20kW Standby Generator: Real Specs

    Oct 19, 2026
    Best Solar Panels for Cloudy Climates: What Actually Matters

    Best Solar Panels for Cloudy Climates: What Actually Matters

    Oct 02, 2026
    Pallet of boxed solar panels in shrink wrap on a warehouse floor with a liftgate box truck behind

    Solar Panel Pallet Cost, Delivered: $/W Math | PES

    Sep 23, 2026
    Commercial flat-roof solar array with copper grounding lugs bonding aluminum racking rails

    Commercial Solar Grounding BOM: NEC 690.43 | PES

    Sep 23, 2026
    All-black solar panels on a residential shingle rooftop in late afternoon sunlight

    Aptos DNA 460W Panel: Specs, Price & Family | PES

    Sep 23, 2026
    Residential standby generator on a concrete pad beside a brick home with conduit to a wall-mounted transfer switch

    Briggs PowerProtect 13kW Shell + Symphony II ATS | PES

    Sep 23, 2026
    Full wooden pallet stacked with boxed solar panels in shrink film on a warehouse floor with a flatbed liftgate truck behind

    Buying Solar Panels by the Pallet: Pro Guide | PES

    Sep 23, 2026
    Wall-mounted hybrid solar inverter in a tidy residential utility room with metal conduit, red and black battery cables and a subpanel

    Sol-Ark vs GoodWe Hybrid Inverter Guide | PES

    Sep 23, 2026
    Two modern wall-mounted home battery storage units side by side on a clean residential garage wall with conduit and a disconnect

    EG4 Battery vs Tesla Powerwall 3: Honest Comparison | PES

    Sep 23, 2026
    Caribbean-style home in Puerto Rico with a rooftop solar array and a wall-mounted home battery, palm trees and bright sun

    Puerto Rico Solar + Battery Resilience Guide | PES

    Sep 23, 2026
    All-black residential rooftop solar panels with a uniform busbar-free surface on a shingle roof

    AIKO Solar Panels: Price, Specs & ABC Technology | PES

    Sep 23, 2026
    Commercial ground-mount bifacial solar array on light gravel under a clear sky

    Bila Solar AA-530US: Domestic Content Panels & ITC | PES

    Sep 23, 2026
    Gloved hand clamping a split-core current transformer around a conductor inside an open electrical panel

    Accu-CT Split-Core Sensors Explained: 333mV CTs | PES

    Sep 23, 2026
    Floor-standing home battery storage cabinet beside a wall-mounted hybrid inverter in a residential garage

    Big Battery NEXUS 15kWh Explained: Specs & Scaling | PES

    Sep 23, 2026
    Through-the-wall PTAC air conditioner installed on a hotel guestroom wall beneath a large window

    Amana PTAC Sizing Guide: 7,000–15,000 BTU Ladder | PES

    Sep 23, 2026
    Residential standby generator on a composite pad beside a suburban home with an electrician work van in the driveway

    Champion aXis Generator Guide: 8.5kW, 14kW & 22kW | PES

    Sep 23, 2026
    Air-cooled home standby generator on a composite pad with electrician connecting the fuel line

    Generac 7042 & 7172 Explained: /817 and /997 Shells | PES

    Sep 22, 2026
    Modular home battery stack with inverter head and subpanel in a utility room

    Bluetti Buying Guide: AC180P vs AC200PL vs EP900 | PES

    Sep 22, 2026
    All-black residential solar panels on a shingle rooftop at low afternoon sun

    Canadian Solar 445W vs 435W: TOPHiKu6 Model Guide | PES

    Sep 22, 2026
    Portable power station with expansion battery and folding solar panel in a residential garage

    Anker SOLIX Buying Guide: C2000 Gen 2 vs F3800 vs E10 | PES

    Sep 22, 2026
    Electric unit heater mounted high on the wall of a residential garage workshop with metal conduit

    Solar Garage Heater Sizing Calculator | PES

    Sep 20, 2026
    Electrician testing a 240V receptacle with a digital multimeter in a workshop with panel behind

    kWh to Amps Calculator: 120V, 240V & 3-Phase | PES

    Sep 20, 2026
    Home battery storage unit wall-mounted in a garage charging from rooftop solar with hybrid inverter

    Solar Battery Charge Time Calculator | PES

    Sep 20, 2026
    Residential standby generator on a concrete pad beside a house at dusk with interior lights on

    What Can a Generator Run? kW Load Calculator | PES

    Sep 20, 2026
    White residential propane tank beside a standby generator on a concrete pad in a suburban backyard

    Propane Tank Sizing for Generators: Calculator | PES

    Sep 19, 2026
    Residential electric meter on an exterior wall beside the service entrance conduit of a suburban home

    Power Consumption Calculator: kWh & Cost | PES

    Sep 19, 2026
    Galvanized round HVAC ducts and flex duct branching across a residential attic with foil insulation

    Duct Size Calculator: CFM Chart by Room & Ton | PES

    Sep 19, 2026
    Electrician measuring current with a clamp meter on a copper conductor inside a residential breaker panel

    Amps to Watts Calculator: 120V, 240V & 12V | PES

    Sep 19, 2026
    Rooftop solar array with conduit down to an open main service panel showing the backfed PV breaker

    Solar 120% Rule Calculator: Max PV Breaker | PES

    Sep 19, 2026
    Commercial standby generator on a concrete pad with a wall-mounted automatic transfer switch

    kVA to kW Calculator: Power Factor Converter | PES

    Sep 19, 2026
    Open residential breaker panel with 240V double-pole breakers and copper feeders of different gauges

    240V Wire Size Calculator: Breaker & Gauge Chart | PES

    Sep 19, 2026
    Electrician pulling THHN copper conductors into EMT conduit on a hot commercial rooftop

    Ampacity Derating Calculator: NEC 310.16 & Heat | PES

    Sep 19, 2026
    Solar charge controller mounted on utility-room wall with battery bank cables

    Solar Charge Controller Sizing Calculator | PES

    Sep 19, 2026
    Residential rooftop solar array with series-string wiring and aluminum racking

    Solar String Sizing: Max Panels in Series | PES

    Sep 19, 2026
    Rooftop air-conditioning condenser unit with electrical disconnect and conduit whip

    MCA vs MOCP: AC Circuit Sizing Calculator | PES

    Sep 19, 2026
    Open residential breaker panel with labeled double-pole breakers and copper feeders

    Breaker Size Calculator: 125% Rule & Wire Chart | PES

    Sep 19, 2026
    Off-grid hybrid inverter with battery rack and conduit runs in a utility room

    Off-Grid Inverter Sizing: Continuous, Surge & Battery | PES

    Sep 18, 2026
    Electrician's hand holding a circuit breaker in front of an open load center

    Breaker Compatibility Chart: QO vs BR vs QP Panels | PES

    Sep 18, 2026
    Row of residential rooftop solar panels in soft daylight, close-up on glass cells

    Solar Panel Wattage Chart: 400W vs 450W vs 500W+ | PES

    Sep 18, 2026
    Automatic transfer switch with thick copper conductors next to breaker panel

    Transfer Switch Wire Sizing: Ampacity Chart by kW | PES

    Sep 18, 2026
    Torque screwdriver tightening a terminal lug on a copper conductor in a panel

    Lug Torque Chart: NEC 110.14 Terminal Tightness by Size &...

    Sep 18, 2026
    Electrical subpanel with feeder cable and neatly dressed branch circuits

    Subpanel Sizing Guide: Feeder Size, Spaces & Load Calc | PES

    Sep 18, 2026
    Residential rooftop solar installation at golden hour with installer tools nearby

    Solar ROI Calculator: Payback, ITC & 25-Year Savings by S...

    Sep 18, 2026
    Standby generator on concrete pad with automatic transfer switch on house wall

    Transfer Switch Sizing Guide: Amps, Circuits & ATS vs Man...

    Sep 18, 2026
    Standby generator beside a residential propane tank and natural gas line

    Standby Generator Fuel Consumption Chart: NG, Propane & D...

    Sep 17, 2026
    Home battery storage wall unit in a garage powering household circuits

    Solar Battery Backup Runtime Calculator: Hours by Load & ...

    Sep 17, 2026
    Service entrance mast and meter base on a residential exterior wall

    Service Entrance Cable Size Calculator: 100A/200A/400A Se...

    Sep 17, 2026
    Green-insulated copper grounding conductors bonded to a ground bar in a panel

    Ground Wire Size Chart: NEC 250.122 EGC Sizing by Breaker...

    Sep 17, 2026
    Thick red and black battery cables with crimped lugs on a battery bank rack

    Battery Cable Size Chart: 12V/24V/48V Inverter & Bank Cab...

    Sep 17, 2026
    Level 2 EV charger wall-mounted in a residential garage with dedicated circuit

    EV Charger Circuit Sizing: NEC 625 Breaker, Wire & Load C...

    Sep 17, 2026

    Get Price Drops & Product Releases

    Weekly digest for installers and project managers — price drops, new stock, NEC code updates.

    Portlandia Electric Supply